User Manual
16 Rockwell Automation Publication 20B-UM002G-EN-P - July 2014
Chapter 1 Programming and Parameters
No. Description
1File – Lists the major parameter file category.
2Group – Lists the parameter group within a file.
3No. – Parameter number. Note that all parameters in the PowerFlex 700VC are 32 bit.
= Parameter value cannot be changed until drive is stopped.
= Parameter only displayed when [Motor Cntl Sel] is set to “4.”
= This parameter only available with firmware version 6.002 and later.
4 Parameter Name & Description – Parameter name as it appears on an LCD HIM, with a brief description of
the parameter’s function.
5Values – Defines the various operating characteristics of the parameter. Three types exist.
ENUM Default:
Options:
Lists the value assigned at the factory. “Read Only” = no default.
Displays the programming selections available.
Bit Bit: Lists the bit place holder and definition for each bit.
Numeric Default:
Min/Max:
Units:
Lists the value assigned at the factory. “Read Only” = no default.
The range (lowest and highest setting) possible for the parameter.
Unit of measure and resolution as shown on the LCD HIM.
Important: Some parameters will have two unit values:
• Analog inputs can be set for current or voltage with [Anlg In Config], param. 320.
• Setting [Speed Units], parameter 79 selects Hz or RPM.
Important: When sending values through DPI ports, simply remove the decimal point to arrive at
the correct value (i.e. to send “5.00 Hz,” use “500”).
6 Related – Lists parameters (if any) that interact with the selected parameter. The symbol “ ” indicates that
additional parameter information is available in Appendix C.
12 3 4 5 6 7 8
File
Group
No.
Parameter Name & Description Values
Related
UTILITY
Drive . . .
198 [Load Frm Usr Set]
Loads a previously saved set of parameter values
from a selected user set location in drive
nonvolatile memory to active drive memory.
Default:
Options:
0
0
1
2
3
“Ready”
“Ready”
“User Set 1”
“User Set 2”
“User Set 3”
199
Diagnostics
216 [Dig In Status]
Status of the digital inputs.
Read Only 361
…
366
MOTOR . . .
Torq . . .
434 [Torque Ref B Mult]
Defines the value of the multiplier for the
[Torque Ref B Sel] selection.
Default:
Min/Max:
Units:
1.0
–/+32767.0
0.1
053
000000xxxxxxxxxx
10 01234567891112131415
1 = Input Present
0 = Input Not Present
x = Reserved
Bit #
Digital In1
Digital In2
Digital In3
Digital In4
Digital In5
Digital In6
FV
FV