Appendix C Application Notes
Voltage Tolerance
Drive Rating Nominal Line
Voltage
Nominal Motor
Voltage
Drive Full Power
Range
Drive Operating
Range
200…240 200 200* 200…264 180…264
208 208 208…264
240 230 230…264
380…480 380 380* 380…528 342…528
400 400 400…528
480 460 460…528
500…600
(Frames 0…4 Only)
600 575* 575…660 432…660
500…690
(Frames 5 & 6 Only)
600 575* 575…660 475…759
690 690 690…759 475…759
Drive Full Power Range = Nominal Motor Voltage to Drive Rated Voltage +10%.
Rated power is available across the entire Drive Full Power Range.
Drive Operating Range = Lowest (*) Nominal Motor Voltage –10% to Drive Rated Voltage +10%. Drive
Output is linearly derated when Actual Line Voltage is less than the Nominal
Motor Voltage.
EXAMPLE
Calculate the maximum power of a 5 Hp, 460V motor connected to a 480V
rated drive supplied with 342V Actual Line Voltage input.
Actual Line Voltage / Nominal Motor Voltage = 74.3%
74.3% × 5 Hp = 3.7 Hp
74.3% × 60 Hz = 44.6 Hz
At 342V Actual Line Voltage, the maximum power the 5 Hp, 460V motor can
produce is 3.7 Hp at 44.6 Hz.
HP @ Motor (Drive Output)
Actual Line Voltage (Drive Input)
Full Power Range
Drive Operating Range
Nominal Motor Voltage -10%
Nominal Motor Voltage
Derated Power Range
Drive Rated Voltage
Drive Rated Voltage +10%
5 HP
3.7 HP
HP @ Motor (Drive Output)
Actual Line Voltage (Drive Input)
342V
460V
480V
528V