User guide
Rockwell Automation Publication 20A-IN009D-EN-P - June 2013 21
PowerFlex 70 Adjustable Frequency AC Drive
Cable Entry Plate Removal
If additional wiring access is needed, the cable entry plate on all drive frames can
be removed. Loosen the screws securing the plate to the heat sink and slide the
plate out.
Figure 8 - Frame A, B, C, D Power Terminal Block and DC Bus Test Points
Figure 9 - Frame E Power Terminal Block
Figure 10 - Power Input Terminals on Frame B with Internal RFI Filter Option
Terminal Description Notes
R R (L1) Three-phase AC line input power.
For single-phase input, connect to any two terminals.
SS (L2)
TT (L3)
BR1 DC brake DB resistor connection - Important: Do not connect both an internal and
external DB resistor at the same time. This can violate the minimum
allowed DB resistance and cause damage to the drive.
BR2 DC brake
U U (T1) To the motor
V V (T2) To the motor
W W (T3) To the motor
PE PE ground –
PE PE ground –
-DC DC bus (–)
➊Test point on Frames A, B, C, and D are to the left or right of the power
terminal block. Frame E has a dedicated terminal.
+DC DC bus (+) –