Installation Instruction Owner's manual

Kinetix 350 Single-axis EtherNet/IP Servo Drives 13
Rockwell Automation Publication 2097-IN008D-EN-P - July 2013
Ground Your Kinetix 350 Drive to the Subpanel
If the Kinetix 350 drive is mounted on a painted subpanel, ground to a bonded cabinet ground
bus with a braided ground strap or 4.0 mm
2
(12 AWG) solid-copper wire, 100 mm (3.9 in.) long.
Connecting the Braided Ground Strap
For dimensions, see Kinetix 350 Drive Mounting Dimensions on page 6.
ATTENTION: To avoid personal injury and equipment damage, verify the following:
Installation complies with specifications regarding wire types, conductor sizes, branch circuit
protection, and disconnect devices. The National Electrical Code (NEC) and local codes outline
provisions for safely installing electrical equipment.
Motor power connectors are used only for connection purposes. Do not use motor power
connectors to turn the unit on and off.
Shielded power cables are grounded to prevent potentially high voltages on the shield.
Bonded Cabinet
Ground Bus
Ground Grid or Power
Distribution Ground
Braided
Ground Strap
Ground Stud