User Manual Owner manual

Publication 2093-UM001A-EN-P — January 2007
Connecting the Kinetix 2000 Drive System 77
Wiring the LIM Connectors
This section provides examples and wiring tables to assist you in making
connections to the line interface module (LIM) connectors.
Wiring the Auxiliary Input Power (APL) Connector
The Auxiliary Input Power (APL) connector is present only on the
2094-XL75S-Cx models.
Line Interface Module (APL connector)
Auxiliary Input Power (APL) Connector
Wiring the VAC LINE (IPL) Connector
Line Interface Module (IPL connector)
L2/N
L1
1 2
Line Interface Module, Top View
(2094-XL75S-Cx is shown)
Single-phase Supply APL Pin Signal
Recommended Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
Nm (lb-in.)
L1 1 L1
0.2....0 (24...10) 7.0 (0.28) 0.5...0.6 (4.4...5.3)
L2 2 L2/N
L3
L2
L1
1 2 3 4
Line Interface Module, Top View
(2094-XL75S-Cx is shown)