DC Common Bus Applications 213
Setting the Additional Bus
Capacitance Parameter
In this procedure you will set the Add Bus Cap parameter using DriveExplorer
software.
The following hardware and software tools are required to provide the
necessary communication link between your personal computer and the
Kinetix 2000 drive system running DriveExplorer software.
Remove SERCOS Communication
Follow these steps to remove (break) SERCOS communications.
1. Remove three-phase and control power from the Kinetix 2000 drive
system.
2. Remove one of the SERCOS fiber-optic cables.
Fiber-optic cable connections (Tx and Rx) are located on the top of each
IAM/AM.
3. Reapply three-phase and control power.
Set the Additional Bus Capacitance Parameter
Follow these steps to set the Additional Bus Capacitance parameter.
1. Start your DriveExplorer software.
2. From the menu bar choose Explore\Connect\Local or enter Ctrl-L
from the keyboard.
Description Catalog Numbers Version
DriveExplorer software
(1) (2)
(1)
Refer to DriveExplorer Getting Results Manual, publication 9306-GR001, for instructions.
(2)
Additional information regarding these communication and software tools is available at
http://www.ab.com/support/abdrives
.
9306-4EXP02ENE 5.02 or later
Anacanda Serial to DPI Adapter
(2) (3)
(3)
Refer to 1203-SSS (series B) FRN 3.xxx User Manual, publication 20COMM-UM001, for instructions.
1203-SSS (Series B) 3.004 or later
RSLogix 5000 Software 9324-RLD300NE 16.0 or later
ATTENTION
To avoid personal injury or equipment damage, at least one end of a
SERCOS fiber-optic cable must be disconnected from the drive. This
ensures that motion will not occur while changes are being made to
the Add Bus Cap parameter.