DC Common Bus Applications
Introduction
This appendix provides integration procedures specific to the Kinetix 2000
multi-axis servo-drive systems configured for dc common bus. The procedure
involves calculating capacitance values and setting the Add Bus Cap parameter
using DriveExplorer software.
Before You Begin
These procedures assume you have mounted and wired your Kinetix 2000 dc
common bus system.
Before you set the Additional Bus Capacitance (Add Bus Cap) parameter in
DriveExplorer software, you need to calculate the following values:
Total bus capacitance, and
Additional bus capacitance.
Topic Page
Before You Begin 209
Calculating Total Bus Capacitance 210
Calculating Additional Bus Capacitance 210
Kinetix 2000 Capacitance Values 211
Common Bus Capacitance Example 212
Setting the Additional Bus Capacitance Parameter 213