Upgrading Firmware 197
13. Select the workstation (01 in the preceding diagram) and click OK.
Drive Executive should connect with the drive and begin to upload the
Kinetix 2000 parameters.
A parameter upload initially occurs, followed by a file group upload.
Each upload displays in a separate screen.
TIP
Upload time varies. It is based on the number of axes on the
power rail and the baud rate of the 1203-SSS.
For example, a baud rate of 38400 requires approximately
25 minutes to upload a six-axis Kinetix 2000 system.