194 Upgrading Firmware
6. Configure the RS232 DF1 Device as shown.
The baud rate for a 1203-SSS device is often written on the back label. If
the baud rate is not found, you should attempt to connect by entering
different baud rates.
• Select the correct baud rate for the device. The diagram shows
38,400 as the correct baud rate.
• Verify the correct Comm Port is selected for your pc. No conflicting
programs should be using this port at this time. For example, RSLinx
should not be open at this time.
• The SCANport must be listed as the Device, and the octal Station
Number is 01.
7. Select Auto-Configure.