156 Specifications and Dimensions
Auxiliary Control Power Specifications
This section lists auxiliary control power requirements for a Kinetix 2000
system comprised of an IAM, up to seven AMs, a Shunt Module, or a Slot
Filler.
Auxiliary Control Power Specifications
Number of AMs
(2093-AMPx or
2093-AMx)
Current Requirements
(115V ac)
Current Requirements
(230V ac) Max Inrush Input VA
0 0.3 A 0.15 A
93 A
50 VA
1 0.6 A 0.30 A 99 VA
2 0.9 A 0.45 A 148 VA
3 1.2 A 0.60 A 197 VA
4 1.5 A 0.75 A 247 VA
5 1.8 A 0.90 A 296 VA
6 2.1 A 1.05 A 345 VA
7 2.4 A 1.20 A 395 VA
Shunt Module
(2093-ASP06)
2.5 A 1.25 A 410 VA
Slot Filler
(2093-PRF)
— — — —