Manual
1 Publication 2090-IN002B-EN-P — February 2006
Installation Instructions
300 W Active Shunt Regulator
The 300 W Active Shunt Regulator is used in systems that see
significant dc voltage regeneration from large inertial load
applications. The Allen-Bradley Ultra3000, Ultra5000, and ULTRA 100
drives (see table below) do not have internal shunt circuitry to
dissipate excess energy, resulting in overvoltage faults. For the
smooth braking of large inertial loads, the use of a shunt regulator is
recommended.
The active shunt (catalog number 2090-UCSR-A300
or 1398-SR3AF)
can be used with the following drive products.
The active shunt monitors the dc bus voltage of the drive. If the
voltage reaches activation level, the shunt drops the dc bus voltage
and dissipates the energy as heat. Figure 1 illustrates the drop in dc
bus voltage.
Figure 1
Shunt Activation on DC Bus Voltage
Drive Family Cat. No.
Ultra3000 Drives
2098-DSD-005, -005-SE, -005-DN, -010, -010-SE, -010-DN, -020, -020-SE,
-020-DN, -005X, -005X-DN, -010X, -010X-DN, -020X and -020X-DN
Ultra5000 Drives 2098-IPD-005, -005-DN, -010, -010-DN, -020, and -020-DN
ULTRA 100 Drives
1398-DDM-005, -005-DN, -009, -009-DN, -019, -019-DN, -005X, -005X-DN,
-009X, -009X-DN, -019X, and -019X-DN
Voltage Drop for 1.0 ms, min
Time
Actual Shunt Time
Activation Level
Bus Voltage