User guide

10 Micro800 8-Point Input and 8-Point Output AC Modules
Publication 2085-IN005B-EN-P - September 2012
Status indicators 8 yellow indicators
Isolation voltage 150V (continuous), Reinforced
Insulation Type, channel to
system
Type tested at 1950V DC for 60 s
240V (continuous), Reinforced Insulation Type, channel
to system
Type tested at 3250V DC for 60 s
North American temp code T4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1.
(2)
RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Input Specifications – 2005-IA8 and 2085-IM8
Attribute 2085-IA8 2085-IM8
Number of Inputs 8
Voltage category 120V AC 240V AC
Operating voltage range 74…120V AC 159…240V AC
Off-state voltage, max 20V AC 40V AC
Off-state current, max 2.5 mA
On-state current, min 5.0 mA @ 74V AC 4.0 mA @ 159V AC
On-state current, max 12.5 mA @ 120V AC 7.0 mA @ 240V AC
Input impedance, max 22.2 kΩ
Inrush current, max 450 mA
Input filter time
Off to On
On to Off
20 ms
IEC type compliance Type 3
Output Specifications - 2085-OA8
Attribute Value
Number of Outputs 8
Voltage category 120V/230V AC
Operating voltage range 120…240V AC
Output voltage, min 85V AC
Output voltage, max 240V AC
Off-state current, max 2.5 mA
On-state current, min 10 mA per output
On-state current, max 0.5 A per output
On-state current,
per module, max
4 A
General Specifications
Attribute 2085-IA8 2085-IM8 2085-OA8