Installation Instructions Micro850 48 Point Programmable Controllers Catalog Numbers 2080-LC50-48AWB, 2080-LC50-48QWB, 2080-LC50-48QBB, 2080-LC50-48QVB http://rockwellautomation.com/literature FR IT DE ES Cette publication est disponible en français sous forme électronique (fichier PDF). Pour la télécharger, rendez-vous sur la page Internet indiquée ci-dessus. Questa pubblicazione è disponibile in Italiano in formato PDF. Per scaricarla collegarsi al sito Web indicato sopra.
Micro850 48 Point Programmable Controllers Important User Information Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://rockwellautomation.
Micro850 48 Point Programmable Controllers 3 Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11.
Micro850 48 Point Programmable Controllers North American Hazardous Location Approval The following modules are North American Hazardous Location approved: 2080-LC50-48AWB, 2080-LC50-48QWB, 2080-LC50-48QBB, 2080-LC50-48QVB The following information applies when operating this equipment in hazardous locations: Informations sur l’utilisation de cet équipement en environnements dangereux: Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous
Micro850 48 Point Programmable Controllers 5 WARNING: • When used in a Class I, Division 2, hazardous location, this equipment must • • • • • • • • be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes. If you connect or disconnect the serial cable with power applied to this module or the serial device on the other end of the cable, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Micro850 48 Point Programmable Controllers ATTENTION: • To comply with the CE Low Voltage Directive (LVD), this equipment must be • powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV). To comply with UL restrictions, this equipment must be powered from a Class 2 or Limited Voltage Limited Current Source (LVLC). ATTENTION: • • • • • The USB and serial cables are not to exceed 3.0 m (9.84 ft).
Micro850 48 Point Programmable Controllers 7 Additional Resources Resource Description Micro830® and Micro850® Programmable A more detailed description of how to install and use your Micro830 and Micro850 programmable controller. Controllers User Manual, publication 2080-UM002 Micro800® AC Power Supply Installation Information on wiring and installing the optional AC power supply.
Micro850 48 Point Programmable Controllers Overview The Micro850 48-point controller is an expandable brick style controller with embedded inputs and outputs. It can accommodate up to five plug-in modules and accommodates any 24V DC output power supply that meets minimum specifications such as the optional Micro800 power supply, 2080-PS120-240VAC.
Micro850 48 Point Programmable Controllers 9 Status Indicator Input status Network status Module status Power status Run status Fault status Force status Serial communications status Output status 45037 Mount the Module Most applications require installation in an industrial enclosure to reduce the effects of electrical interference and environmental exposure.
Micro850 48 Point Programmable Controllers Module Spacing Maintain spacing from objects such as enclosure walls, wireways and adjacent equipment. Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation. If optional accessories/modules are attached such as the power supply 2080-PS120-240VAC or expansion I/O modules, make sure that there is 50.8 mm (2 in.) of space on all sides after attaching the optional parts.
Micro850 48 Point Programmable Controllers 11 Panel Mounting Dimensions 108 (4.25) 108 (4.25) 100 (3.9) Measurements are in millimeters (inches) 45917 Use Surge Suppressors Because of the potentially high current surges that occur when switching inductive load devices, such as motor starters and solenoids, we recommend the use of some type of surge suppression to protect and extend the operating life of the controllers output contacts.
Micro850 48 Point Programmable Controllers Wire the Controller 2080-LC50-48AWB / 2080-LC50-48QWB Input Terminal Block COM0 1 I-01 2 3 I-00 I-03 4 I-06 I-05 5 6 I-02 7 I-04 8 9 COM1 I-08 10 11 I-07 I-10 12 13 I-09 COM2 14 15 I-11 16 I-12 TERMINAL BLOCK 1 I-13 1 I-15 2 3 I-14 I-17 4 I-19 5 6 I-16 7 I-18 I-20 8 9 COM3 I-22 10 11 I-21 I-24 12 13 I-23 I-26 14 15 I-25 16 I-27 TERMINAL BLOCK 3 +DC24 1 CM0 2 3 -DC24 CM1 4 5 CM2 6 O-00 7
Micro850 48 Point Programmable Controllers 13 Control Drawing for Class 1 Division 2 Applications Hazardous Location Class 1 Division 2, Groups A, B, C, and D Non-Hazardous Location Any associated apparatus with Universal Serial Bus (USB) connection Micro800 Controller Vmax = 5V DC Imax = 500 μA Li = 1 μH Ci = 120 pF USB Port J3 USB Port Voc, Isc, La and Ca to be determined per Capacitance and Inductance Values table Capacitance and Inductance Values Nonincendive Equipment Associated Apparatus Vma
Micro850 48 Point Programmable Controllers Specifications General Specifications Attribute 2080-LC50 -48AWB -48QWB Number of I/O 48 (28 inputs, 20 outputs) Dimensions HxWxD 90 x 238 x 80 mm (3.54 x 9.37 x 3.15 in.) Shipping weight, approx. 0.725 kg (1.60 lb) -48QVB -48QBB Wire size Solid and Stranded Min Max 0.2 mm2 2.
Micro850 48 Point Programmable Controllers 15 General Specifications Attribute 2080-LC50 -48AWB Pilot duty rating C300, R150 Isolation voltage 250V (continuous), Reinforced Insulation Type, Output to Aux and Network, Inputs to Outputs. Type tested for 60 s @ 3250V DC Output to Aux and Network, Inputs to Outputs. 150V (continuous), Reinforced Insulation Type, Input to Aux and Network Type tested for 60 s @ 1950V DC Input to Aux and Network.
Micro850 48 Point Programmable Controllers Input Specifications Attribute 2080-LC50-48AWB 2080-LC50-48QWB / 2080-LC50-48QVB / 2080-LC50-48QBB 120V AC Input High Speed DC Input (Inputs 0…11) Standard DC Input (Inputs 12 and higher) Number of inputs 28 12 16 Input group to backplane isolation Verified by the following dielectric tests: 1950V AC for 2 s 150V working voltage (IEC Class 2 reinforced insulation) Verified by the following dielectric tests: 720V DC for 2 s 50V DC working voltage (I
Micro850 48 Point Programmable Controllers 17 Output Specifications Attribute 2080-LC50-48AWB / 2080-LC50-48QWB 2080-LC50-48QVB / 2080-LC50-48QBB Relay Output High Speed Output (Outputs 0...3) Standard Output (Outputs 4 and higher) Number of outputs 20 4 16 Output voltage, min 5V DC, 5V AC 10.8V DC 10V DC Output voltage, max 125V DC, 265V AC 26.4V DC 26.4V DC Load current, min 10 mA Load current, continuous, max 2.0 A 100 mA (high-speed 1.0 A @ 30 °C operation) 0.3 A @ 65 °C 1.
Micro850 48 Point Programmable Controllers Environmental Specifications Attribute Value Temperature, operating IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): -20…65 °C (-4…149 °F) Temperature, surrounding air, max 65 °C (149 °F) Temperature, non-operating IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nono
Micro850 48 Point Programmable Controllers 19 Certifications Certification (when product is marked)(1) Value c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E322657. UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E334470. CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326-1; Meas./Control/Lab.
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.