B-4 Adapter Parameters
16
17
18
19
20
21
22
23
[Flt Cfg A1]
[Flt Cfg A2]
[Flt Cfg B1]
[Flt Cfg B2]
[Flt Cfg C1]
[Flt Cfg C2]
[Flt Cfg D1]
[Flt Cfg D2]
Sets the data that is sent to the Datalink in the
drive if the following is true:
• Parameter 10 - [Comm Flt Action] is set to
Send Flt Cfg and communications are
disrupted.
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.
24
[CRC/BCC Cfg]
Techniques for error detection in data
communications. Must match the technique used
by the software or controller communicating with
the adapter.
Default: 0 = BCC
Bit Values: 0 = BCC
1 = CRC
Type: Read/Write
Reset Required: Yes
25 [CRC/BCC Act]
Actual checksum or CRC selection.
Default: 0 = BCC
Bit Values: 0 = BCC
1 = CRC
Type: Read Only
26 [Dup Msg Detect]
Determines if the adapter ignores duplicate
messages. Normally set to Enable (default). Set to
Disable if using a ProSoft 3150-DFM module or
any device which does not increment the TNS ID.
Default: 1 = Enable
Bit Values: 0 = Disable
1 = Enable
Type: Read/Write
Reset Required: No
Parameter
No. Name and Description Details