User Manual PowerFlex 20-COMM-R Remote I/O Adapter FRN 1.
Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Summary of Changes The information below summarizes the changes made to this manual since its last release (March 2002). Description of Changes Page Reformatted document from half size (5.5 x 8.5 in.) to full size (8.5 x 11 in.) Throughout manual Added information about Connected Components Workbench software configuration tool for drives and connected peripherals.
soc-ii Summary of Changes 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P
Table of Contents Preface About This Manual Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1 Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2 Chapter 1 Getting Started Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ii Table of Contents Chapter 5 Using Block Transfer Messaging About Block Transfer Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 Formatting Block Transfer Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 Executing Block Transfers for Explicit Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 Example Programs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface About This Manual Topic Page Conventions Used in This Manual P-1 Rockwell Automation Support P-2 Additional Resources P-2 This manual provides information about the adapter and using it with PowerFlex 7-Class (Architecture-Class) drives. The adapter can be used with other products that support a DPI™ adapter. See the documentation for your product for specific information about how it works with the adapter.
P-2 About This Manual Rockwell Automation Support Rockwell Automation offers support services worldwide, with over 75 sales and support offices, over 500 authorized distributors, and over 250 authorized systems integrators located throughout the United States alone. In addition, Rockwell Automation representatives are in every major country in the world.
About This Manual P-3 Resource Description PowerFlex 700S w/Phase I Control Installation Manual (Frames 1…6), publication 20D-IN024 PowerFlex 700S w/Phase I Control Installation Manual (Frames 9 and 10), publication PFLEX-IN006 PowerFlex 700S w/Phase I Control User Manual (All Frame Sizes), publication 20D-UM001 PowerFlex 700S w/Phase I Control Reference Manual, publication PFLEX-RM002 PowerFlex 700S w/Phase II Control Installation Manual (Frames 1…6), publication 20D-IN024 PowerFlex 700S w/Phase II Con
P-4 About This Manual Notes: 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P
Chapter 1 Getting Started The adapter is intended for installation into a PowerFlex 7-Class drive and is used for network communication. When used with PowerFlex 750-Series drives, the 20-COMM-R adapter must have firmware revision 1.010 or later, and must be installed using the 20-750-20COMM or 20-750-20COMM-F1 Communication Carrier Card. This manual does include some information on using the 20-COMM-R adapter with PowerFlex 750-Series drives—but there are operating limitations.
1-2 Getting Started Features The features of the adapter include the following: • Typical mounting in a PowerFlex 7-Class drive. • Captive screws to secure and ground the adapter to the drive. • Compatibility with various configuration tools to configure the adapter and connected host drive, including the following tools: – – – – PowerFlex HIM (Human Interface Module) on the drive, if available Connected Components Workbench software, version 1.02 or later DriveExplorer software, version 2.
Getting Started Compatible Products 1-3 At the time of publication, the adapter is compatible with the following products: • PowerFlex 70 drives with standard or enhanced control • PowerFlex 750-Series drives (1) • PowerFlex 700 drives with standard or vector control • PowerFlex Digital DC drives • PowerFlex 700H drives • SMC™ Flex smart motor controllers • PowerFlex 700S drives with Phase I or Phase II control • SMC-50 smart motor controllers • PowerFlex 700L drives with 700 vector control or 70
1-4 Getting Started User-Supplied Equipment To install and configure the adapter, you must supply the following: ❑ A small flathead screwdriver ❑ Remote I/O cable ❑ Drive and adapter configuration tool, such as the following: – PowerFlex 20-HIM-xx HIM – Connected Components Workbench software, version 1.02 or later Connected Components Workbench is the recommended stand-alone software tool for use with PowerFlex drives. You can obtain a free copy by: • Internet download at http://www.ab.
Getting Started Safety Precautions 1-5 Please read the following safety precautions carefully. ! ! ! ! ! ! ! ! ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove all power from the PowerFlex drive, and then verify power has been discharged before installing or removing an adapter. ATTENTION: Risk of injury or equipment damage exists.
1-6 Getting Started Quick Start This section is provided to help experienced users quickly start using the adapter. If you are unsure how to complete a step, see the referenced chapter. Step Action See 1 Review the safety precautions for the adapter. Throughout this manual 2 Verify that the PowerFlex drive is properly installed. Drive User Manual 3 Commission the adapter. Chapter 2, Installing the Adapter a.
Chapter 2 Installing the Adapter This chapter provides instructions for installing the adapter in a PowerFlex 7-Class drive. Topic Page Preparing for an Installation 2-1 Selecting Remote I/O Cables 2-1 Commissioning the Adapter 2-2 Connecting the Adapter to the Drive 2-4 Connecting the Adapter to the Network 2-7 Applying Power 2-8 Preparing for an Installation Before installing the adapter, verify that you have all required equipment. See Required Equipment on page 1-3.
2-2 Installing the Adapter Commissioning the Adapter To commission the adapter, set the Rack Address Rotary Switches and the Configuration DIP Switches. Either set these switches to the desired settings or disable them by sliding Configuration DIP Switches SW7 and SW8 to the ‘On’ position so that adapter parameters can be used instead. Important: New switch settings are recognized only when power is applied to the adapter or it is reset.
Installing the Adapter 2-3 The Rack Address Rotary Switch settings can be verified (as a decimal value) by viewing Diagnostic Device Item number 29 (page 6-4). Setting the Configuration DIP Switches Set the Configuration DIP Switches (Figure 2.2) to match your application specifics for the controller and network. Figure 2.
2-4 Installing the Adapter The settings for all of the Configuration DIP Switches can be verified by viewing Diagnostic Item number 28 (page 6-4). Connecting the Adapter to the Drive ! ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing the adapter. 1. Remove power from the drive. 2. Use static control precautions. 3.
Installing the Adapter Figure 2.3 2-5 DPI Ports and Internal Interface Cables 20-COMM-R Adapter ➊ ➋ ➌ PowerFlex 70 - All Frames ➍ PowerFlex 700 Frames 0 and 1 PowerFlex 700S Frames 0 and 1 PowerFlex 700 Frames 2 and Larger PowerFlex 700S Frames 2 through 6 HIM panel opens to allow access to DPI interface. To open panel, remove screws on left side of HIM panel and swing open. X2 X1 PowerFlex 700H Frames 9 and Larger PowerFlex 700S Frames 9 and Larger Item Description ➊ 15.24 cm (6 in.
2-6 Installing the Adapter Figure 2.4 Mounting and Grounding the Adapter Drive 0.9 N•m (8.0 lb•in) 4 Places Adapter Internal Interface Cable folded behind the adapter and in front of the drive. Ground Tab Detail PowerFlex 70 - All Frame Sizes (Adapter mounts in drive.) 0.9 N•m (8.0 lb•in) 4 Places PowerFlex 700 Frames 0 and 1 PowerFlex 700S Frames 0 and 1 (Adapter mounts on door.) Verify metal ground tab is bent 90° and is under the adapter before tightening screw.
Installing the Adapter Connecting the Adapter to the Network ! 2-7 ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing the adapter. 1. Remove power from the drive. 2. Use static control precautions. 3. Connect a Remote I/O cable to the controller or create a daisy-chain from another device on the Remote I/O network (see Figure 2.5).
2-8 Installing the Adapter 6. If the adapter is at the end of the Remote I/O link, connect a termination resistor (see Figure 2.7). The resistor should have a value of 82 or 150 ohms (82 ohms is preferred). Important: If the Remote I/O network is operating at 230.4 Kbps, an 82 ohm termination resistor must be used. Important: If any of the following products, which cannot operate at 230.4 Kbps, are on the Remote I/O network, a 150 ohm termination resistor must be used. • • • • • • Figure 2.
Installing the Adapter Figure 2.8 2-9 Drive and Adapter Status Indicators (location on drive may vary) PORT MOD ➋ NET A NET B ➊ STS Table 2.A Drive and Adapter Start-Up Status Indications Item Name Color State Description Green Flashing Drive ready but not running, and no faults are present. Steady Drive running, no faults are present. Flashing, drive stopped An inhibit condition exists – the drive cannot be started. Check drive Parameter 214 - [Start Inhibits].
2-10 Installing the Adapter Configuring and Verifying Key Drive Parameters The PowerFlex 7-Class drive can be separately configured for the control and Reference functions in various combinations. For example, you could set the drive to have its control come from a peripheral or terminal block with the Reference coming from the network. Or you could set the drive to have its control come from the network with the Reference coming from another peripheral or terminal block.
Chapter 3 Configuring the Adapter This chapter provides instructions and information for setting the parameters to configure the adapter.
3-2 Configuring the Adapter Using the PowerFlex 7-Class If your drive has either an LED or LCD HIM (Human Interface Module), it can be used to access parameters in the adapter as shown below. We HIM to Access Parameters recommend that you read through the steps for your HIM before performing the sequence. For additional information, see the drive documentation or the PowerFlex 7-Class HIM Quick Reference, publication 20HIM-QR001. Using an LED HIM Step Example Screens 1.
3-3 Configuring the Adapter Setting the Rack Address If adapter Configuration DIP Switches SW7 and SW8 (Figure 2.2) are both set to ‘On’, the value of Parameter 03 - [RIO Addr Cfg] determines the rack address. Note these points: • Although the adapter supports rack addresses between 00 and 77 octal, not all controllers recognize all of the addresses, and a Remote I/O channel can support only 32 devices. • PLC-2 controllers identify rack addresses differently than other controllers.
3-4 Configuring the Adapter Setting the Baud Rate If adapter Configuration DIP Switches SW7 and SW8 (Figure 2.2) are both set to ‘On’, the value of Parameter 05 - [RIO Rate Cfg] determines the Remote I/O baud rate. 1. Set the value of Parameter 05 - [RIO Rate Cfg] to the baud rate at which your network is operating. Port 5 Device 20-COMM-R Parameter #: 05 RIO Rate Cfg 0 57.6 kbps Value Baud Rate 0 57.6 Kbps (default) 1 115.2 Kbps 2 230.4 Kbps 2.
Configuring the Adapter Setting the Last Rack 3-5 If adapter Configuration DIP Switches SW7 and SW8 (Figure 2.2) are both set to ‘On’, the value of Parameter 26 - [Last RIO Rack] notifies the controller that this device is the last device on a specified rack. This parameter must be set to ‘1’ (Enabled) if the drive is the last device on a rack address that uses a PLC-2 controller. We recommend that you set this parameter to ‘1’ (Enabled) whenever a device is the last device on a rack. 1.
3-6 Configuring the Adapter Setting the I/O Configuration The I/O configuration determines the data that is sent to and from the drive. Logic Command/Status, Reference/Feedback, and Datalinks may be enabled or disabled. (Datalinks allow you to read/write directly to parameters in the drive using Discrete I/O.) A ‘1’ enables the I/O and a ‘0’ disables the I/O. 1. Set the bits in Parameter 12 - [DPI I/O Config].
Configuring the Adapter Setting a Fault Action 3-7 By default, when I/O communication is disrupted (for example, a cable is disconnected) or the controller is idle (in program mode or faulted), the drive responds by faulting if it is using I/O from the network.
3-8 Configuring the Adapter Setting the Fault Configuration Parameters When setting Parameter 10 - [Comm Flt Action] or 11 - [Idle Flt Action] to ‘Send Flt Cfg’, the values in the following parameters are sent to the drive after an I/O communication fault and/or idle fault occurs. You must set these parameters to values required by your application. Parameter Description 14 - [Flt Cfg Logic] A 16-bit value sent to the drive for Logic Command.
Configuring the Adapter The following parameters provide information about the status of the adapter. You can view these parameters at any time. Parameter Description 04 - [RIO Addr Actual] The rack address used by the adapter. This will be one of the following values: • The address set by the Rack Address Rotary Switches. • The value of Parameter 03 - [RIO Addr Cfg] if adapter Configuration DIP Switches SW7 and SW8 are both set to ‘On’.
3-10 Configuring the Adapter Updating the Adapter Firmware The adapter firmware can be updated over the network or serially through a direct connection from a computer to the drive using a 1203-USB or 1203-SSS serial converter. When updating firmware over the network, you can use the Allen-Bradley ControlFLASH software tool, the built-in update capability of DriveExplorer Lite or Full software, or the built-in update capability of DriveExecutive software.
Chapter 4 Using Discrete and Block Transfer I/O This chapter provides information and examples about using I/O to control a connected PowerFlex drive.
4-2 Using Discrete and Block Transfer I/O Understanding the I/O Image Figure 4.1 (1/4 rack) and Figure 4.2 (1/2 rack) show how data is transmitted between a controller and drive. Rack Size Reference Source Feedback Destination Datalinks 1/4 Block Transfer I/O Block Transfer I/O Block Transfer I/O 1/2 Discrete I/O Discrete and Block Transfer I/O Block Transfer I/O Figure 4.
Using Discrete and Block Transfer I/O Figure 4.
4-4 Using Discrete and Block Transfer I/O Discrete I/O Image The Discrete I/O image is either a 1/4 rack or 1/2 rack. Use Configuration DIP Switch SW4 to select 1/4 rack or 1/2 rack or, if the hardware switches have been disabled, adapter Parameter 27 - [Rack Size]. The I/O that is transmitted depends on the size of the rack. Figure 4.1 shows a 1/4 rack I/O image, and Figure 4.2 shows a 1/2 rack I/O image.
Using Discrete and Block Transfer I/O Size Valid Values 16-bit -32768 to 32767 32-bit -2147483648 to 2147483647 4-5 PowerFlex 70/700/700H, and PowerFlex 700L Drives with 700 Control The Reference/Feedback value is a scaled engineering value; it is not in Hertz or RPM. The Reference uses a ‘32767’ scale. The ‘32767’ endpoint of the scale is equal to the value of drive parameter 55 - [Maximum Freq], which has a default value of 130 Hz.
4-6 Using Discrete and Block Transfer I/O If parameter 82 - [Maximum Speed] is changed to 90 Hz, then: 90 Hz = 32767 Speed Feedback uses the same scaling as the speed Reference. TIP: For PowerFlex 700 drives with vector control, firmware 3.xxx or later, parameter 299 - [DPI Fdbk Select] enables you to select the feedback data coming from the drive over DPI. The default is ‘Speed Fdbk’ in Hz or RPM determined by Parameter 079 - [Speed Units].
Using Discrete and Block Transfer I/O Block Transfer I/O Image 4-7 The Block Transfer I/O image is a Block Transfer message that contains eighteen 16-bit words. It reserves two words for the Reference/Feedback and four words for each Datalink (in case 32-bit values are used). Figure 4.
4-8 Using Discrete and Block Transfer I/O drive. If a request has fewer than eighteen words, as much I/O data as will fit in the request will be used. Reference/Feedback in Block Transfer I/O Image Word 0 and word 1 are reserved for the Reference/Feedback. The size of the Reference (16-bits or 32-bits) is determined by the drive. If a 16-bit Reference (Figure 4.3) is used, word 1 is not used during writes and is read as zero (0) during reads.
Using Discrete and Block Transfer I/O 4-9 Datalink Scaling PowerFlex 70/700/700H Drives and PowerFlex 700L Drives with 700 Control Datalink scaling is not automatic and uses whole numbers (INTs or DINTs). See the drive documentation to determine the unit resolution for the associated parameter Datalink. For example, PowerFlex 700VC drive parameter 3 - [Output Current] has a 0.1 unit resolution.
4-10 Using Discrete and Block Transfer I/O In this example, the Parameter 10 - [Elapsed Run Time] value of 6553.9 Hrs is read as ‘6553.9’ in Datalink A1 Out (Parameter 310) and Datalink A2 Out (Parameter 311). Datalink Word Parameter Data (Hex) A1 Out LSW 10 0003 A2 Out MSW 10 0001 Conversion Example: Parameter 010 - [Elapsed Run Time] = 6553.9 Hrs MSW = 0001hex = 0001binary = 216 = 65536 LSW = 0003hex =3 Engineering Value = 65536 + 3 = 65539 Parameter 10 Displayed Value = 6553.
Using Discrete and Block Transfer I/O Example Ladder Logic Program Information 4-11 The example ladder logic programs in the sections of this chapter are intended for and operate PowerFlex 70 or PowerFlex 700 drives with the 20-COMM-R adapter in a 1/4 rack configuration. Functions of the Example Programs The example programs enable you to do the following: • Receive Logic Status information from the drive. • Send a Logic Command to control the drive (for example, start, stop).
4-12 Using Discrete and Block Transfer I/O ControlLogix Controller Example Figure 4.5 ControlLogix Example Ladder Logic for Main Routine Get the drive's logic status, feedback, and datalink outputs. See Figure 4.6 for ControlLogix Block Transfer I/O Read. JSR Jump To Subroutine Routine Name BT_IO_Read 0 This subroutine contains the user's control logic. See Figure 4.7 for ControlLogix I/O User Logic.
Using Discrete and Block Transfer I/O Figure 4.7 4-13 ControlLogix Example I/O User Ladder Logic Get the drive's Logic Status word. COP Copy File Source The20CommR:I.Data[1] Dest DriveLogicStatus Length 1 0 Read Active, Faulted, and At Speed drive status bits and place in respective tags. 1 2 3 4 DriveLogicStatus.1 DriveStatusActive DriveLogicStatus.7 DriveStatusFaulted DriveLogicStatus.10 DriveStatusAtSpeed Transfer Start, Stop, Jog, and Clear command tags into drive's output image.
4-14 Using Discrete and Block Transfer I/O Figure 4.8 ControlLogix Example Ladder Logic for Block Transfer I/O Write Place the desired Reference in the block transfer output structure. COP Copy File Source DriveReference Dest DriveBTOutputImage[0] Length 1 0 1 Place the desired Datalink A input values into the block transfer output structure. Add similar rungs to use Datalinks B, C, and D.
4-15 Using Discrete and Block Transfer I/O PLC-5 Controller Example Figure 4.9 0000 PLC-5 Example Ladder Logic for Main Routine This rung handles the logic needed to stop the drive upon the user's command. As shown, the user STOP input must be a normally closed pushbutton. If the drive is running, pressing the STOP button will seal the stop command bit until the drive comes to a complete stop.
4-16 Using Discrete and Block Transfer I/O Figure 4.10 PLC-5 Example Ladder Logic for Block Transfer I/O (Read/Write) This run executes an I/O BTR to move status information from the 20-COMM-R to the PLC. Note that this is the minimum logic needed -- a more complex system may require additional sequencing logic.
Using Discrete and Block Transfer I/O SLC 500 Controller Examples 4-17 Examples in this section are provided for SLC 500 Series C controllers with firmware revision 3.xx and higher, and for SLC 500 controllers all versions. Series C Controller with Firmware Revision 3.xx and Higher In a series C, firmware revision 3.xx and higher SLC processor, Block Transfer Read (BTR) and Block Transfer Write (BTW) instructions can be used.
4-18 Using Discrete and Block Transfer I/O Block Transfer Write Example The following data is used for this example. • • • • • • Rack 1 Group 4 (upper half rack) Slot 0 (always 0) Control Block N10:0 (user defined) Data File N22:0 (user defined) Buffer File M0:x.200 (Block Transfer Writes always start with M0, where x is the slot in which the 1747-SN scanner card is in. In this example, the 1747-SN card is in slot 2.) • Requested Word Count is 18 or less (see See Figure 4.1 on page 4-2 or See Figure 4.
Using Discrete and Block Transfer I/O 4-19 All Controller Versions The SLC RIO scanner performs Block Transfers through control/status buffers that you allocate in the scanner’s M0 and M1 files. The first 10 words of each file are reserved for either control words (M0) or status words (M1). Block Transfer Read/Write data starts in word 11. See the Remote I/O 1747-SN Scanner User Manual, publication 1747-UM013, for more information. The following data is required for the example program.
4-20 Using Discrete and Block Transfer I/O Figure 4.13 SLC 500 Example Ladder Logic for Main Routine (I/O User Logic) continued This rung moves the Reference from the User Operator Station to the Block Transfer Write file where it is moved to the drive by Block Transfer. MOV Move Source 0004 Dest This rung moves the READY status bit from the drive to the user display. 0005 N7:1 30000 < N10:10 30000 < User DRIVE READY Status N7:10 Drive READY Status I:1.
Using Discrete and Block Transfer I/O 4-21 Figure 4.14 SLC 500 Example Ladder Logic for Block Transfer I/O Write This rung executes once each time the SLC is switched into RUN mode. It resets any BTW control bits that might be set in the RIO scanner. I/O BTW Control MOV Move Source First Pass S:1 0000 15 0 0< N10:0 -32768 < Dest COP Copy File Source Dest Length #N10:0 #M0:1.100 28 This rung transfers the Block Transfer Write (BTW) status buffer from the RIO scanner to the memory in the SLC.
4-22 Using Discrete and Block Transfer I/O Figure 4.15 SLC 500 Example Ladder Logic for Block Transfer I/O Read This rung executes once each time the SLC is switched into RUN mode. It resets any BTR control bits that might be set in the RIO scanner. First Pass S:1 MOV Move Source 0000 15 128 128 < N11:0 -32640 < Dest COP Copy File Source Dest Length #N11:0 #M0:1.200 28 This rung transfers the Block Transfer Read (BTR) status buffer from the RIO scanner to the memory in the SLC.
Chapter 5 Using Block Transfer Messaging This chapter provides information and examples for using Block Transfer to send Explicit Messages to control, configure, and monitor a PowerFlex 7-Class drive on a Remote I/O network.
5-2 Using Block Transfer Messaging About Block Transfer Messaging Block Transfer messaging is used to transfer data to the drive. The size of Block Transfer messages to the Remote I/O adapter determines their purpose. Words Type Used For See 18 or fewer I/O Reference/Feedback and Datalinks Chapter 4 20, 30, or 60 Explicit Configuring and monitoring data This chapter Other Not Recognized Do not use or an error will occur.
Using Block Transfer Messaging 5-3 See Block Transfer Read Structure to Receive Block Transfer Messages on page 5-4 for a description of each word in a Block Transfer Read used to receive an Explicit Message response. Block Transfer Write Structure to Send Block Transfer Messages Data Field Description Word 0 Length The least significant byte contains the length of the Explicit Message. The most significant byte is always zero.
5-4 Using Block Transfer Messaging Block Transfer Read Structure to Receive Block Transfer Messages Data Field Description Word 0 Length The least significant byte contains the length of the actual Explicit Message in bytes. The most significant byte is always zero.
Using Block Transfer Messaging 1. Enter data into the program. Data must be entered into a data file for a program to run. The data file that is used depends on your controller and application. 2. Run the program. When executing a Block Transfer message, the program must monitor the Block Transfer Status word (Word 0) in the Discrete I/O Image. Its bits are defined as shown in the following table.
5-6 Using Block Transfer Messaging The following table describes the main events and what a program is monitoring when performing Block Transfer messaging. Item Event Description ➊ BTW Request Before initiating a Block Transfer message, bit 8 must be 1. This setting indicates that the adapter and drive are communicating, so a Block Transfer message will reach the drive. Before initiating a Block Transfer Write message, bit 9 must be 1.
Using Block Transfer Messaging ControlLogix Controller Example 5-7 Data Format for a Read and Write Parameter The data in this example is for a PowerFlex 70 drive at Remote I/O rack. The following set of arrays shows a read of drive parameter 1 - [Output Freq]. The value of parameter 1 is 213 (21.3 Hz).
5-8 Using Block Transfer Messaging Ladder Logic Program Figure 5.3 ControlLogix Example Ladder Logic for Block Transfer Messaging Make a local copy of the block transfer status word to avoid it changing mid-scan. COP Copy File Source The20CommR:I.Data[0] Dest BlockTransferStatus Length 1 0 When the user enables the SendMessageRequest tag, start the message logic.
Using Block Transfer Messaging PLC-5 Controller Example 5-9 Block Transfer Data Files for PLC-5 Example Program The following set of data files shows a read of drive parameter 1 - [Output Freq]. The value of parameter 1 is 213 (21.3 Hz).
5-10 Using Block Transfer Messaging Ladder Logic Program Figure 5.4 PLC-5 Example Ladder Logic for Block Transfer Messaging The user initiates a messaging transaction by setting the User Execute Message Input bit true. This causes one messaging BTW to be sent to the 20-COMM-R. User EXECUTE MESSAGE Input N7:2 0000 0001 Execute Message B3:0 B3:0 ONS L 1 0 0 This rung causes one messaging BTW to execute when the 20-COMM-R is ready to receive a Messaging BTW and the user has requested the BTW.
Using Block Transfer Messaging SLC 500 Controller Examples 5-11 Examples in this section are provided for SLC 500 Series C controllers with firmware revision 3.xx and higher, and for SLC 500 controllers all versions. Block Transfer Data Files for Example Program—Series C Controller with Firmware Revision 3.xx and Higher In a series C, firmware revision 3.xx and higher SLC processor, Block Transfer Read (BTR) and Block Transfer Write (BTW) instructions can be used.
5-12 Using Block Transfer Messaging Response and Control Data to Write to Drive Parameter 41 (Hex) Address Value (hex) Description See Page N13:0 0002 Length of Message = 2 bytes 5-4 N13:1 0000 N13:2 0000 The Message was Successful 5-4 Figure 5.5 SLC 500 Series C, FRN 3.xx and Higher, Example Ladder Logic for Block Transfer Read and Block Transfer Write The following data is used for this example.
Using Block Transfer Messaging 5-13 Block Transfer Data Files for Example Program—All SLC Versions The following set of data files shows a read of drive parameter 1 - [Output Freq]. The value of parameter 1 is 213 (21.3 Hz).
5-14 Using Block Transfer Messaging Block Transfers are handled differently in the SLC 500 controller and require the following data for the example program. Address Value (decimal) Description N12:1 20 Block Transfer Write Length N12:2 100 Rack 1, Group 0, Slot 0 N13:1 20 Block Transfer Read Length N13:2 100 Rack 1, Group 0, Slot 0 See Formatting Block Transfer Messages on page 5-2 for more information on block transfer messages. Ladder Logic Program Figure 5.
Using Block Transfer Messaging Figure 5.6 5-15 SLC 500 Example Ladder Logic for Block Transfer Messaging - continued This rung executes once each time the SLC is switched into RUN mode. It resets any BTR control bits that might be set in the RIO scanner. First Pass S:1 0005 15 MOV Move Source 128 128 < N13:0 128 < Dest COP Copy File Source Dest Length #N13:0 #M0:1.400 74 This rung transfers the Block Transfer Read (BTR) status buffer from the RIO scanner to the memory in the SLC.
5-16 Using Block Transfer Messaging Notes: 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P
Chapter 6 Troubleshooting This chapter provides information for diagnosing and troubleshooting potential problems with the adapter and network. Understanding the Status Indicators Topic Page Understanding the Status Indicators 6-1 PORT Status Indicator 6-2 MOD Status Indicator 6-2 NET A Status Indicator 6-3 Viewing Adapter Diagnostic Items 6-3 Viewing and Clearing Events 6-5 The adapter has three status indicators. They can be viewed on the adapter or through the drive cover.
6-2 Troubleshooting PORT Status Indicator This red/green bicolor LED indicates the status of the adapter’s connection to the drive as shown in the table below. Status Cause Corrective Action Off The adapter is not powered or is not properly connected to the drive. • Securely connect the adapter to the drive using the Internal Interface (ribbon) cable. • Apply power to the drive. Flashing Red The adapter is not receiving a ping message from the drive.
6-3 Troubleshooting NET A Status Indicator Status Off This red/green bicolor LED indicates the status for the Remote I/O network connection as shown in the table below. Cause The adapter is not powered or is not properly connected to the network. Corrective Actions • Securely connect the adapter to the drive using the Internal Interface (ribbon) cable and to the network using a Remote I/O cable. • Correctly connect the Remote I/O network cable to the 3-pin Remote I/O plug.
6-4 Troubleshooting Table 6.A Adapter Diagnostic Items No. Name 1 Common Logic Cmd Description The present value of the Common Logic Command being transmitted to the drive by this adapter. If this diagnostic item is any value other than 1, the values of items 7 through 14 (Datalink A1 In through Datalink D2 In) are not actually being transferred to the drive. 2 Prod Logic Cmd The present value of the Product Logic Command being transmitted to the drive by this adapter from the controller.
Troubleshooting Viewing and Clearing Events 6-5 The adapter has an event queue to record significant events that occur in the operation of the adapter. When such an event occurs, an entry is put into the event queue. You can view the event queue with any of these drive configuration tools: • • • • LCD PowerFlex 7-Class HIM Connected Components Workbench software, version 1.02 or later DriveExplorer software, version 2.01 or later DriveExecutive software, version 1.
6-6 Troubleshooting Events Many events in the event queue occur under normal operation. If you encounter unexpected communications problems, the events may help you or Allen-Bradley personnel troubleshoot the problem. The following events may appear in the event queue. Table 6.B Adapter Events Code Event Description 1 No Event Empty event queue entry. 2 DPI Bus Off Flt A bus-off condition was detected on DPI. This event may be caused by loose or broken cables or by noise.
Appendix A Specifications This appendix presents the specifications for the adapter. Communications Topic Page Communications A-1 Electrical A-1 Mechanical A-1 Environmental A-1 Regulatory Compliance A-2 Network Protocol Network Baud Rate Remote I/O 57.6 Kbps, 115.2 Kbps, or 230.4 Kbps Available baud rates depend on the length of the Remote I/O cable. See Selecting Remote I/O Cables on page 2-1 for more information.
A-2 Specifications Regulatory Compliance Certification Specification UL UL508C cUL CE (1) CTick (1) CAN / CSA C22.2 No. 14-M91 EN50178 and EN61800-3 EN61800-3 The PowerFlex 70 drive passes Second Environment/Industrial. If First Environment/Restricted is needed for radiated emissions, then a ferrite core (Fair-Rite part number 2643102002 or equivalent) must be added to the Remote I/O cable. The PowerFlex 700 drive passes First and Second Environment without the ferrite core.
Appendix B Adapter Parameters This appendix provides information about the adapter parameters. For configuration tools to monitor or change parameter values of the drive, adapter, and other connected peripherals, see Configuration Tools on page 3-1. Parameter List Parameter No. Name and Description 01 02 03 [DPI Port] Displays the port to which the adapter is connected. This will usually be port 5.
B-2 Adapter Parameters Parameter No. Name and Description Details [Reset Module] Default: Values: 09 No action if set to ‘0’ (Ready). Resets the adapter if set to ‘1’ (Reset Module). Restores the adapter to its factory default settings if set to ‘2’ (Set Defaults). This parameter is a command. It will be reset to ‘0’ (Ready) after the command has been performed. ! 10 ATTENTION: Risk of injury or equipment damage exists.
B-3 Adapter Parameters Parameter No. Name and Description [DPI I/O Config] Details Datalink D Datalink C Datalink B Datalink A Cmd/Ref Bit Definition Not Used xxx0 0001 0 = I/O Disabled 1 = I/O Enabled Type: Read/Write Reset Required: Yes Not Used Default: Sets the I/O that is transferred through the adapter.
B-4 Adapter Parameters Parameter No. Name and Description 16 17 18 19 20 21 22 23 [Flt Cfg A1 In] [Flt Cfg A2 In] [Flt Cfg B1 In] [Flt Cfg B2 In] [Flt Cfg C1 In] [Flt Cfg C2 In] [Flt Cfg D1 In] [Flt Cfg D2 In] Sets the data that is sent to the Datalink in the drive if any of the following is true: • Parameter 10 - [Comm Flt Action] is set to ‘4’ (Send Flt Cfg) and I/O communication is disrupted. • Parameter 11 - [Idle Flt Action] is set to ‘4’ (Send Flt Cfg) and the controller is idle.
Appendix C CIP Objects This appendix presents information about the CIP (Common Industrial Protocol) objects that can be accessed for Block Transfer messages. For information on the format of Block Transfer messages and example ladder logic programs, see Chapter 5, Using Block Transfer Messaging. Topic Class Code Hex. CIP Services Common Messages CIP Services Page Dec.
C-2 CIP Objects Common Messages The following table lists messages that are commonly used to view and edit information in a device. Other messages can be sent using the values within each object listed. All values are in decimal.
CIP Objects DPI Device Object C-3 Class Code Hexadecimal Decimal 0x92 146 Instances The number of instances depends on the number of components in the device. The total number of components can be read in Instance 0, Class Attribute 4. Description Class Attributes (Drive) Drive Component 1 Drive Component 2 … Example 0 1 2 16384 16385 Class Attributes (Adapter) Adapter Component 1 … Device Host Adapter DPI Port 1 DPI Port 2 DPI Port 3 DPI Port 4 DPI Port 5 DPI Port 6 … (Dec.
C-4 CIP Objects Attribute ID Access Rule Name 13 Read Only Character Set Code Data Type BYTE 15 Read Only Languages Supported 16 Read Only Date of Manufacture 17 Read Only Product Revision 18 19 Read Only Read/Write Serial Number Language Selected STRUCT of: BYTE BYTE[n] STRUCT of: WORD BYTE BYTE STRUCT of: BYTE BYTE DWORD BYTE 20 Read/Write Customer-Generated Firmware STRING[36] 128 129 130 Read Only Read Only Read Only Customization Code Customization Revision Number Customization D
CIP Objects DPI Parameter Object C-5 Class Code Hexadecimal Decimal 0x93 147 Instances Example 0 1 2 Description Class Attributes (Drive) Drive Parameter 1 Attributes Drive Parameter 2 Attributes … Device Host Adapter DPI Port 1 DPI Port 2 DPI Port 3 DPI Port 4 DPI Port 5 DPI Port 6 16384 16385 Class Attributes (Adapter) Adapter Parameter 1 Attributes … (Dec.) 0…16383 16384…17407 17408…18431 18432…19455 19456…20479 20480…21503 21504…22527 22528…23551 … Instances (Hex.
C-6 CIP Objects Instance Attributes Attribute ID 7 Access Rule Read Only Name DPI Online Read Full 8 9 10 11 Read Only Read/Write Read/Write Read/Write DPI Descriptor DPI Parameter Value DPI RAM Parameter Value DPI Link 12 13 Read Only Read Only Help Object Instance DPI Read Basic 14 15 16 Read Only Read/Write Read Only (1) (2) (3) Data Type STRUCT of: BOOL[32] CONTAINER(1) CONTAINER CONTAINER CONTAINER WORD WORD STRING[4] UINT UINT UINT INT BYTE[3] BYTE STRING[16] BOOL[32] Various Various BYT
CIP Objects C-7 Descriptor Attributes Bit 0 1 2 Name Data Type (Bit 1) Data Type (Bit 2) Data Type (Bit 3) 3 Sign Type 4 Hidden 5 Not a Link Sink 6 Not Recallable 7 ENUM 8 Writable 9 Not Writable When Enabled 10 Instance 11 12 13 14 15 16 17 18 Reserved Decimal Place (Bit 0) Decimal Place (Bit 1) Decimal Place (Bit 2) Decimal Place (Bit 3) Extended Data Type (Bit 1) Extended Data Type (Bit 2) Extended Data Type (Bit 3) 19 20 21 22 23 24 25 26 Parameter Exists Not Used Formula Links Ac
C-8 CIP Objects Formulas for Converting Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10 Decimal Places) Internal Value = ((Display Value x Divisor x 10 Decimal Places) / (Multiplier x Base)) - Offset Object-Specific Services Service Code Implemented for: Class Instance 0x4B (1) Yes No 0x4C (1) Yes No 0x4D (2) Yes No 0x4E (2) Yes No (1) (2) 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P Service Name Get_Attributes_Scattered Set_Attributes_Scattere
CIP Objects C-9 Format for Get_Attributes_Scattered Service The structure shown below can get up to eighteen parameters in a single message. In the Response Message, a parameter number with the high bit set indicates that the associated parameter value field actually contains a DPI error code.
C-10 CIP Objects Continued from previous page.
CIP Objects C-11 The data in this example is for a Get_Attributes_Scattered of PowerFlex 70 parameters 1 - [Output Freq], 3 - [Output Current] and 6 - [Output Voltage] from a device at node address 1.
C-12 CIP Objects Format for Set_Attributes_Scattered Service The structure shown below can set up to eighteen parameters in a single message. In the Response Message, a parameter number with the high bit set indicates that the associated pad word field contains an error code.
CIP Objects C-13 Continued from previous page.
C-14 CIP Objects The data in this example is for a Set_Attributes_Scattered of PowerFlex 70 parameters 140 - [Accel Time 1], 142 - [Decel Time 1] and 100 - [Jog Speed] to a device at node address 1.
CIP Objects DPI Fault Object C-15 Class Code Hexadecimal Decimal 0x97 151 Products such as PowerFlex drives use this object for faults. Adapters use this object for events. Instances Example 0 1 2 Description Class Attributes (Drive) Most Recent Drive Fault Second Most Recent Drive Fault … Device Host Adapter DPI Port 1 DPI Port 2 DPI Port 3 DPI Port 4 DPI Port 5 DPI Port 6 16384 16385 Class Attributes (Adapter) Most Recent Adapter Event … (Dec.
C-16 CIP Objects Instance Attributes Attribute ID 0 1 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P Access Rule Read Only Read Only Name Full/All Information Basic Information Data Type STRUCT of WORD STRUCT of: BYTE BYTE STRING[16] STRUCT of: LWORD BOOL[16] WORD CONTAINER[n] STRUCT of: WORD STRUCT of: BYTE BYTE STRUCT of: LWORD BOOL[16] Description Fault code Fault source DPI port DPI Device Object Fault text Fault time stamp Timer value (0 = timer not supported) BOOL[0]
CIP Objects DPI Alarm Object C-17 Class Code Hexadecimal Decimal 0x98 152 Products such as PowerFlex drives use this object for alarms or warnings. Adapters do not support this object. Instances Example 0 1 2 Description Class Attributes (Drive) Most Recent Alarm Second Most Recent Alarm … Instances (Hex.) (Dec.) Device 0x0000…0x3FFF 0…16383 Host Only host devices can have alarms. … The number of instances depends on the maximum number of alarms supported by the queue.
C-18 CIP Objects Instance Attributes Attribute ID 0 1 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P Access Rule Read Only Read Only Name Data Type Full/All STRUCT of Information WORD STRUCT of: BYTE BYTE STRING[16] STRUCT of: LWORD BOOL[16] WORD CONTAINER[n] Basic STRUCT of Information WORD STRUCT of: BYTE BYTE STRUCT of: LWORD BOOL[16] Description Alarm code Alarm source DPI port DPI Device Object Alarm text Alarm time stamp Timer value (0 = timer not supported) BOOL[0]: (
CIP Objects DPI Time Object C-19 Class Code Hexadecimal Decimal 0x9B 155 Instances The number of instances depends on the number of timers in the device. Instance 1 is always reserved for a real-time clock although a device may not support it. The total number of timers can be read in Instance 0, Attribute 2.
C-20 CIP Objects Notes: 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P
Appendix D Logic Command/Status Words This appendix presents the definitions of the Logic Command and Logic Status words that are used for some products that can be connected to the adapter. If the Logic Command/Logic Status for the product that you are using is not listed, refer to your product’s documentation.
D-2 Logic Command/Status Words Logic Status Word Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x (1) x x x x x See ‘Owners’ in drive User Manual for further information. 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P 0 x Status Ready Active Command Direction Actual Direction Accel Decel Alarm Fault At Speed Local Control (1) Reference Description 0 = Not Ready (Par.
Logic Command/Status Words PowerFlex 700S (Phase II Control) and 700L (with 700S Control) Drives D-3 Logic Command Word Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x x x x x x 0 x Command Normal Stop Start (1) Jog 1 Clear Fault (2) Unipolar Direction Description 0 = Not Normal Stop 1 = Normal Stop 0 = Not Start 1 = Start 0 = Not Jog using [Jog Speed 1] (Par. 29) 1 = Jog using [Jog Speed 1] (Par.
D-4 Logic Command/Status Words Logic Status Word Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x x x x x x (1) 0 x Status Active Running Command Direction Actual Direction Accel Decel Jogging Fault Alarm Flash Mode Run Ready At Limit (1) Tach Loss Sw At Zero Spd At Setpt Spd Enable Description 0 = Not Active 1 = Active 0 = Not Running 1 = Running 0 = Reverse 1 = Forward 0 = Reverse 1 = Forward 0 = Not Accelerating 1 = Accelerating 0 = Not Decelerating 1 = Decelerating 0 = No
Logic Command/Status Words D-5 PowerFlex 750-Series Drives Important: When using a 20-COMM-R adapter with a PowerFlex 750-Series drive, the upper word (bits 16…31) of the Logic Command and Logic Status words are not accessible and cannot be used.
D-6 Logic Command/Status Words Logic Status Word Logic Bits 31…15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x x x x x x 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P 0 Command x Run Ready Active Command Direction Actual Direction Accelerating Decelerating Alarm Fault At Setpt Spd Manual Spd Ref ID 0 Spd Ref ID 1 Spd Ref ID 2 Spd Ref ID 3 Spd Ref ID 4 Reserved Description 0 = Not Ready to Run (Par.
Logic Command/Status Words D-7 PowerFlex Digital DC Drives Logic Command Word Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x x x x x x 0 x Command Stop (1) Start (1)(2) Jog Clear Faults Direction Local Control MOP Increment Accel Rate Decel Rate Reference Select (3) MOP Decrement Description 0 = Not Stop 1 = Stop 0 = Not Start 1 = Start 0 = Not Jog (Par.
D-8 Logic Command/Status Words Logic Status Word Logic Bits 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x (1) x x x x x See ‘Owners’ in drive User Manual for further information. 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P 0 x Status Ready Description 0 = Not Ready (Par.
Glossary A Adapter Devices such as drives, controllers, and computers usually require a network communication adapter to provide a communication interface between them and a network such as Remote I/O. An adapter reads data on the network and transmits it to the connected device. It also reads data in the device and transmits it to the network. The 20-COMM-R Remote I/O adapter connects PowerFlex 7-Class drives to a Remote I/O network.
G-2 Glossary CIP (Common Industrial Protocol) CIP is the transport and application layer protocol used by some scanners on Remote I/O networks. The protocol is used for implicit messaging (real-time I/O) and Block Transfer messaging (configuration, data collection, and diagnostics). Client/Server Network This type of network has a server respond to client requests. For example, the Remote I/O adapter is a server of data and responds to the requests of client devices (for example, controllers).
Glossary G-3 DPI Peripheral A device that provides an interface between DPI and a network or user. Peripheral devices are also referred to as ‘adapters’ or ‘modules’. The 20-COMM-R adapter, 1203-USB or 1203-SSS converter, and PowerFlex 7-Class HIMs (20-HIM-xx) are examples of DPI peripherals. DPI Product A device that uses the DPI communication interface to communicate with one or more peripheral devices. For example, a motor drive such as a PowerFlex 7-Class drive is a DPI product.
G-4 Glossary H HIM (Human Interface Module) A device that can be used to configure and control a drive. PowerFlex 7-Class HIMs (catalog number 20-HIM-xx) can be used to configure PowerFlex 7-Class drives and their connected peripherals. Hold Last When communication is disrupted (for example, a cable is disconnected), the adapter and PowerFlex drive can respond by holding last. Hold last results in the drive receiving the last data received via the network connection before the disruption.
Glossary P G-5 Ping A message that is sent by a DPI product to its peripheral devices. They use the ping to gather data about the product, including whether it can receive messages and whether they can log in for control. PowerFlex 7-Class (Architecture Class) Drives The Allen-Bradley PowerFlex 7-Class family of drives supports DPI and, at the time of publication, includes the PowerFlex 70, PowerFlex 700, PowerFlex 700H, PowerFlex 700S, PowerFlex 700L, and PowerFlex 7000.
G-6 Glossary Remote I/O Network Remote I/O is an Allen-Bradley network interface originally designed to link remote I/O racks to PLCs over appropriate cables (‘Blue-Hose’). Remote I/O supports remote, time-critical control communications between a client controller and server devices such as a Remote I/O adapter and its connected host drive. A server device will accept only the packets that are addressed to it. Remote I/O also supports Block Transfer messaging.
Index A adapter applying power, 2-8 commissioning, 2-2 compatible products, 1-3 components, 1-1 configuration tools, 3-1 configuring with parameters, 3-3 to 3-8 switches, 2-2, 2-3 connecting to the drive, 2-4 network, 2-7 definition, G-1 features, 1-2 firmware updating, 3-10 grounding, 2-6 installation, 2-1 to 2-10 mounting on the drive, 2-6 parameters, B-1 to B-4 resetting, 3-8 specifications, A-1 viewing its status, 3-9 applying power to the adapter, 2-8 attentions, 1-5 B baud rate definition, G-1 relati
Index-2 D Datalink Size parameter, B-1 Datalinks definition, G-2 enabling in the adapter, 3-6 in Block Transfer I/O, 4-8 decimal/octal equivalent rack addresses, 3-3 diagnostic items, 6-3 dimensions, A-1 disabling all hardware switches, 2-3 Discrete I/O Block Transfer Control/Status words, 4-4 image for 1/2 rack configuration, 4-3 1/4 rack configuration, 4-2 Logic Command/Status, 4-4 Reference/Feedback, 4-4 DPI connector on adapter, 1-1 data rates, A-1 definition, G-2 Internal Interface cable, 2-4, 2-5 per
Index-3 I I/O about, 4-1 Block Transfer I/O image for 16-bit Reference and Datalinks, 4-7 32-bit Reference and Datalinks, 4-7 configuring the adapter for, 3-6 definition, G-4 Discrete I/O image for 1/2 rack configuration, 4-3 image for 1/4 rack configuration, 4-2 using Discrete and Block Transfer I/O, 4-1 to 4-20 idle action, G-4 Idle Flt Action parameter, B-2 installation applying power to the adapter, 2-8 commissioning the adapter, 2-2 connecting to the drive, 2-4 network, 2-7 preparing for, 2-1 Internal
Index-4 PORT status indicator locating, 6-1 troubleshooting with, 6-2 RIO Rate Actual parameter, B-1 power consumption, A-1 RSLogix 5/500/5000 software, G-5 PowerFlex drives compatible with adapter, 1-3 definition, G-5 HIM, 3-2 installing adapter on, 2-4 preparing for an installation, 2-1 processor, see controller programmable logic controller, see controller Q quick start, 1-6 R rack address definition, G-5 setting with parameter, 3-3 setting with Rack Address Rotary Switches, 2-2 rack size definiti
Index-5 U update definition, G-6 guidelines, 3-10 W website Connected Components Workbench software, G-2 DriveExecutive software, G-3 DriveExplorer software, G-3 DriveTools SP software, G-3 related documentation, P-2 RSLogix 5/500/5000 software, G-5 wiring, see cables Z zero data configuring the adapter for, 3-7 definition, G-6 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P
Index-6 20-COMM-R Remote I/O Adapter User Manual Publication 20COMM-UM004D-EN-P
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support you can find technical and application notes, sample code, and links to software service packs. You can also visit our Support Center at https://rockwellautomation.custhelp.com/ for software updates, support chats and forums, technical information, FAQs, and to sign up for product notification updates.