User Manual
Using the I/O 5-27
20-COMM-C/Q ControlNet Adapter User Manual
Publication 20COMM-UM003F-EN-P
PowerFlex 700 Drives with Vector Control and PowerFlex 700L Drives with 700
Control
When using these drives, which contain DINT (32-bit format) data types,
you will read from and write to the LSW data table address in the controller.
Table 5.K PLC-5 Data Table Addresses for:
PowerFlex 700 Drives with Vector Control
PowerFlex 700L Drives with 700 Control
Data Table Address Description
N9:0 Logic Status (see Appendix D)
N9:1 Speed Feedback
N9:2 Value of parameter assigned to Parameter 310 [Data Out A1] LSW
N9:3 Value of parameter assigned to Parameter 310 [Data Out A1] MSW
N9:4 Value of parameter assigned to Parameter 311 [Data Out A2] LSW
N9:5 Value of parameter assigned to Parameter 311 [Data Out A2] MSW
N9:6 Value of parameter assigned to Parameter 312 [Data Out B1] LSW
N9:7 Value of parameter assigned to Parameter 312 [Data Out B1] MSW
N9:8 Value of parameter assigned to Parameter 313 [Data Out B2] LSW
N9:9 Value of parameter assigned to Parameter 313 [Data Out B2] MSW
N9:10 Value of parameter assigned to Parameter 314 [Data Out C1] LSW
N9:11 Value of parameter assigned to Parameter 314 [Data Out C1] MSW
N9:12 Value of parameter assigned to Parameter 315 [Data Out C2] LSW
N9:13 Value of parameter assigned to Parameter 315 [Data Out C2] MSW
N9:14 Value of parameter assigned to Parameter 316 [Data Out D1] LSW
N9:15 Value of parameter assigned to Parameter 316 [Data Out D1] MSW
N9:16 Value of parameter assigned to Parameter 317 [Data Out D2] LSW
N9:17 Value of parameter assigned to Parameter 317 [Data Out D2] MSW
N10:0 Logic Command (see Appendix
D)
N10:1 Speed Reference
N10:2 Value of parameter assigned to Parameter 300 [Data In A1] LSW
N10:3 Value of parameter assigned to Parameter 300 [Data In A1] MSW
N10:4 Value of parameter assigned to Parameter 301 [Data In A2] LSW
N10:5 Value of parameter assigned to Parameter 301 [Data In A2] MSW
N10:6 Value of parameter assigned to Parameter 302 [Data In B1] LSW
N10:7 Value of parameter assigned to Parameter 302 [Data In B1] MSW
N10:8 Value of parameter assigned to Parameter 303 [Data In B2] LSW
N10:9 Value of parameter assigned to Parameter 303 [Data In B2] MSW
N10:10 Value of parameter assigned to Parameter 304 [Data In C1] LSW
N10:11 Value of parameter assigned to Parameter 304 [Data In C1] MSW
N10:12 Value of parameter assigned to Parameter 305 [Data In C2] LSW
N10:13 Value of parameter assigned to Parameter 305 [Data In C2] MSW
N10:14 Value of parameter assigned to Parameter 306 [Data In D1] LSW
N10:15 Value of parameter assigned to Parameter 306 [Data In D1] MSW
N10:16 Value of parameter assigned to Parameter 307 [Data In D2] LSW
N10:17 Value of parameter assigned to Parameter 307 [Data In D2] MSW