User guide

Troubleshooting 7-3
MOD Status Indicator
Status Cause Corrective Action
Off The adapter is not
powered.
Securely connect the adapter to the
PowerFlex drive using the ribbon cable.
Apply power to the drive and network.
Flashing Red The adapter has failed the
firmware test.
Cycle power to the drive. Parameter settings
may have been changed.
Clear faults in the adapter.
If cycling power does not correct the
problem, the parameter settings may have
been corrupted. Reset defaults and
reconfigure the module.
If resetting defaults does not correct the
problem, flash the adapter with the latest
firmware release.
Solid
Red
The adapter has failed the
hardware test.
Cycle power to the drive.
Replace the adapter.
Flashing Green The adapter is operational
but is not transferring I/O
data.
Place the scanner in RUN mode.
Configure the adapter for the program in the
controller.
Program the controller to recognize and
transmit I/O to the adapter.
Solid Green The adapter is operational
and transferring I/O data.
No Action.
NET A Status Indicator
Status Cause Corrective Actions
Off The adapter is not powered
or is not connected
properly to the network.
Securely connect the adapter to the drive
using the Internal Interface cable and to the
network using a PROFIBUS cable.
Correctly connect the PROFIBUS cable to
the PROFIBUS connector.
Apply power to the drive.
Flashing Red Error in PROFIBUS
configuration.
Re-configure the PROFIBUS module.
Solid Red Error in PROFIBUS
controller initialization.
Cycle power to the drive.
Re-configure the Profibus scanner.
Solid Green The adapter is properly
connected and
communicating on the
network.
No action required.
20COMM-UM006A-EN-P.book Page 3 Friday, September 28, 2001 10:43 AM