User guide

B-4 Adapter Parameters
15
16
17
18
19
20
21
22
[Flt Cfg A1]
[Flt Cfg A2]
[Flt Cfg B1]
[Flt Cfg B2]
[Flt Cfg C1]
[Flt Cfg C2]
[Flt Cfg D1]
[Flt Cfg D2]
Sets the data that is sent to the Datalink in the
drive if any of the following is true:
Parameter 09 - [Comm Flt Action] is set to
Send Flt Cfg and the scanner is put into
Program mode.
Parameter 10 - [Idle Flt Action] is set to Send
Flt Cfg and communications are disrupted.
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses 16-bit
Datalinks, the most significant word of this
value must be set to zero (0) or a fault will
occur.
23 [Parameter Mode]
Sets the format used when performing explicit
messages:
Par Prot (Parameter Protocol) is used to read
or write single parameters.
DPI Par Prot is reserved for future use.
Performing explicit messaging requires the
Parameter Access module to be added when
configuring the node with a network software tool.
Default: 0 = Par Prot
Values: 0 = Par Prot
1 = DPI Par Prot
Type: Read/Write
Reset Required: No
24 [P-DP State]
Displays the state of the Profibus controller.
Default: N/A
Values: 0 = WAIT_PRM
1 = WAIT_CFG
2 = DATA_EX
3 = ERROR
Type: Read Only
Parameter
No. Name and Description Details
20COMM-UM006A-EN-P.book Page 4 Friday, September 28, 2001 10:43 AM