Adapter Parameters B-3
20-COMM-L LonWorks Adapter User Manual
Publication 20COMM-UM008B-EN-P
09 [DPI I/O Cfg]
Sets the I/O that is transferred through the adapter.
NOTE: The Cmd/Ref bit must be set to control the
drive via the network. The respective Datalink bit(s)
must be set if the nvi/nvo Datalink variables are used.
Default: xxx0 0001
Bit Values: 0 = I/O disabled
1 = I/O enabled
Type: Read/Write
Reset Required: Yes
10 [DPI I/O Act]
Displays the I/O that the adapter is actively
transmitting. The value of this parameter is usually
equal to the value of Parameter 9 - [DPI I/O Cfg].
Default: xxx0 0001
Bit Values: 0 = I/O disabled
1 = I/O enabled
Type: Read Only
11 [Flt Cfg Logic]
Sets the Logic Command data that is sent to the drive
if Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and communication is disrupted.
The bit definitions depend on the product to which the
adapter is connected. See Appendix
C or the
documentation for the drive being used.
Default: 0000 0000 0000 0000
Minimum: 0000 0000 0000 0000
Maximum: 1111 1111 1111 1111
Type: Read/Write
Reset Required: No
12 [Flt Cfg Ref]
Sets the Reference data that is sent to the drive if
Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and communication is disrupted.
NOTE: This is a linear engineering unit value where ‘0’
equals 0 Hz. and 32,767 equals the Hz. value in the
PowerFlex 7-Class drive parameter 55 - [Maximum
Freq].
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses a 16-bit
Reference, the most significant word of
this value must be set to zero (0) or a
fault will occur.
13
14
15
16
17
18
19
20
[Flt Cfg A1 In]
[Flt Cfg A2 In]
[Flt Cfg B1 In]
[Flt Cfg B2 In]
[Flt Cfg C1 In]
[Flt Cfg C2 In]
[Flt Cfg D1 In]
[Flt Cfg D2 In]
Sets the data that is sent to the Datalink in the drive if
Parameter 6 - [Comm Flt Action] is set to ‘4’ (Send
Flt Cfg) and communication is disrupted.
NOTE: These are 32-bit values. If 16-bit Datalinks are
active, only the least significant word is used. If the
32-bit value is out of range for a 16-bit Datalink, a
configuration error forces a correction before I/O can
be enabled.
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Default: 0
Minimum: 0
Maximum: 4294967295
Type: Read/Write
Reset Required: No
Important: If the drive uses 16-bit
Datalinks, the most significant word of
this value must be set to zero (0) or a
fault will occur.
Parameter
No. Name and Description Details
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A
Cmd/Ref
Default xxx00001
Bit 76543210
Bit
Definition
Not Used
Not Used
Not Used
Datalink D
Datalink C
Datalink B
Datalink A
Cmd/Ref
Default xxx00001
Bit 76543210