7-6 Using Datalinks with All Protocols
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Note that certain drives may utilize 32-bit datalinks. In this case, Datalinks
are not supported by the adapter. The adapter will support only 15-bit
Datalink values.
Siemens P1 FLN Datalinks Out: A…D
P1 FLN devices work only with 15-bit integer values; therefore, these
points only show 15-bit values. If an adapter is connected to a host using
32-bit Datalinks, the adapter will be prevented from using Datalinks. The
DPI host determines if 16- or 32-bit Datalink values are used.
Siemens P1 FLN Datalinks In: A…D
P1 FLN devices work only with 15-bit integer values; therefore, these
points only show 15-bit values. If an adapter is connected to a host using
32-bit Datalinks, the adapter will be prevented from using Datalinks. The
DPI host determines if 16- or 32-bit Datalink values are used.
!
ATTENTION: Risk of injury or equipment damage exists. On
P1 FLN networks, 16-bit values are truncated to 15-bit values.
Unpredictable operation may result from using non-16-bit drive
parameters with the configurable points. Recognize the data
range limitation of P1 FLN and understand the data value ranges
of each parameter to be accessed over the network. Refer to the
drive user manual for information about drive parameter sizes.
Table 7.M Siemens P1 FLN Datalinks Out: A…D
Point
Number
(1)
(1)
Point numbers that appear in braces { } may be unbundled at the field panel.
Point
Type Descriptor
Factory
Default Description
{44} LAI DLINK A1 OUT 0 Bit 0…14 of Datalink Out A1
{46} LAI DLINK A2 OUT 0 Bit 0…14 of Datalink Out A2
{48} LAI DLINK B1 OUT 0 Bit 0…14 of Datalink Out B1
{50} LAI DLNK B2 OUT 0 Bit 0…14 of Datalink Out B2
{52} LAI DLNK C1 OUT 0 Bit 0…14 of Datalink Out C1
{54} LAI DLNK C2 OUT 0 Bit 0…14 of Datalink Out C2
{56} LAI DLNK D1 OUT 0 Bit 0…14 of Datalink Out D1
{58} LAI DLNK D2 OUT 0 Bit 0…14 of Datalink Out D2
Table 7.N Siemens P1 FLN Datalinks In: A…D
Point
Number
(1)
(1)
Point numbers that appear in braces { } may be unbundled at the field panel.
Point
Type Descriptor
Factory
Default Description
{62} LAO DLNK A1 IN 0 Bits 0…14 of Datalink In A1
{64} LAO DLNK A2 IN 0 Bits 0…14 of Datalink In A2
{66} LAO DLNK B1 IN 0 Bits 0…14 of Datalink In B1
{68} LAO DLNK B2 IN 0 Bits 0…14 of Datalink In B2
{70} LAO DLNK C1 IN 0 Bits 0…14 of Datalink In C1
{72} LAO DLNK C2 IN 0 Bits 0…14 of Datalink In C2
{74} LAO DLNK D1 IN 0 Bits 0…14 of Datalink In D1
{76} LAO DLNK D2 IN 0 Bits 0…14 of Datalink In D2