User Manual
6-4 Using Siemens Building Technologies P1 FLN
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Table 6.B Siemens Building Technologies P1 FLN Point List (Continued)
Point
Number
(1)
(1)
Points not listed are not used in this application. Point numbers that appear in braces { } may be unbundled.
Point
Type
(2)
(2)
For a description of point types, refer to Table 6.A on page 6-2. Note that the outputs and inputs are from the network perspective, not the drive perspective. For example, an LAO is an output from the controller on
the network, but it is an input to the drive.
Descriptor
English
Units Slope Intercept ON Text OFF Text Default Range COV
(3)
(3)
COV indicates whether the points is able to support COVs and overrides.
Description
{46} LAI DLNK A2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out A2.
{48} LAI DLNK B1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out B1.
{50} LAI DLNK B2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out B2.
{52} LAI DLNK C1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out C1.
{54} LAI DLNK C2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out C2.
{56} LAI DLNK D1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out D1.
{58} LAI DLNK D2 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out D2.
{60} LAI INPUT REF 1 0.001 -16.383 0 0 – 32767 Yes Shows the Input Reference 1 parameter.
{61} LAI INPUT REF 2 0.001 -16.383 0 0 – 32767 Yes Shows the Input Reference 2 parameter.
{62} LAO DLNK A1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In A1.
{64} LAO DLNK A2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In A2
{66} LAO DLNK B1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In B1.
{68} LAO DLNK B2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In B2.
{70} LAO DLNK C1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In C1.
{72} LAO DLNK C2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In C2.
{74} LAO DLNK D1 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In D1.
{76} LAO DLNK D2 IN 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink In D2.
{89} LAO LOGIC CMD LO 1 0 0 0 – 255 Yes Lower 8 bits of Product Logic Command Word.
{90} LAO LOGIC CMD HI 1 0 0 0 – 255 Yes Higher 8 bits of Product Logic Command Word.
{91} LAI FEEDBACK 1 0 0 0 – 32767 Yes Feedback value bits 0-14 (absolute value).
{92} LAO REFERENCE 1 0 0 0 – 32767 Yes Reference value bits 0-14.
{93} LDI OK.FAULT 1 0 FAULT OK 0 (OK) 0 – 1 Yes Shows if the drive is faulted or not.
{94} LDO RESET FAULT 1 0 RESET NORMAL 0 (NORMAL) 0 – 1 Yes Resets the fault condition in the drive. Special point.
Will return to NORMAL (0) automatically.
{95} LAI LOGIC STS LO 1 0 0 0 – 255 Yes Lower 8 bits of Product Logic Status Word.
{96} LAI LOGIC STS HI 1 0 0 0 – 255 Yes Higher 8 bits of Product Logic Status Word.
{99} LAO ERROR STATUS 1 0 0 0 – 255 Yes Not used by this application.