User Manual

Using Siemens Building Technologies P1 FLN 6-3
20-COMM-H RS-485 HVAC Adapter User Manual
Publication 20COMM-UM009D-EN-P
Siemens Building Technologies P1 FLN Point Map
Table 6.B Siemens Building Technologies P1 FLN Point List
Point
Number
(1)
(1)
Points not listed are not used in this application. Point numbers that appear in braces { } may be unbundled.
Point
Type
(2)
(2)
For a description of point types, refer to Table 6.A on page 6-2. Note that the outputs and inputs are from the network perspective, not the drive perspective. For example, an LAO is an output from the controller on
the network, but it is an input to the drive.
Descriptor
English
Units Slope Intercept ON Text OFF Text Default Range COV
(4)
(4)
COV indicates whether the points is able to support COVs and overrides.
Description
01 LAO CTRL ADDRESS 1 0 99 0 – 255 No Node address of this device.
02 LAO APPLICATION 1 0 2718 0 – 32767 No Firmware application number.
{03} LAI FREQ OUTPUT HZ 0.01 -163.83 0 0 – 32767 Yes Drive speed in frequency (Hertz).
{04} LAI PCT OUTPUT PCT 0.1 0 0 0 – 32767 Yes Drive speed in percentage of max.
{05} LAI SPEED RPM 1 0 0 0 – 32767 Yes Drive speed in RPM.
{06} LAI CURRENT AMPS 0.1 0 0 0 – 32767 Yes Drive current consumption in amps.
{07} LAI TORQUE PCT 0.1 -1638.3 0 0 – 32767 Yes Drive torque in percentage of max.
{08} LAI POWER KW 0.1 0 0 0 – 32767 Yes Drive power in kW.
{09} LAI DRIVE TEMP DEG C 0.1 -1638.3 0 0 – 32767 Yes Drive temperature in degree C.
{11} LAI DRIVE MWH MWH 0.1 0 0 0 – 32767 Yes Drive total power consumption in MWH.
{12} LAI RUN TIME HRS 0.1 0 0 0 – 32767 Yes Drive total run time in hours.
{13} LAI DC BUS VOLT VOLTS 0.1 0 0 0 – 32767 Yes Drive DC bus voltage.
{20} LAO OVRD TIME 1 0 0 0 – 255 Yes Not used by this application.
{21} LDI FWD.REV MON 1 0 REV FWD 0 (FWD) 0 – 1 Yes Monitor the rotation direction of the drive.
{22} LDO CMD FWD.REV 1 0 REV FWD 0 (FWD) 0 – 1 Yes Command the rotation direction of the drive.
{23} LDI RUN.STOP MON 1 0 RUN STOP 0 (STOP) 0 – 1 Yes Monitor the Run/Stop status of the drive.
{24} LDO CMD RUN.STOP 1 0 RUN STOP 0 (NO) 0 – 1 Yes Command Run to the drive. A STOP issues a
momentary Stop command to the drive.
{25} LDI READY 1 0 READY NOTRDY 0 (NOTRDY) 0 – 1 Yes Monitor the Ready status of the drive.
{26} LDO RUN ENABLE 1 0 ENABLE STOP 0 (NO) 0 – 1 Yes Must be set to ENABLE to allow controlling the drive.
{29} LDO DAY.NGT 1 0 NIGHT DAY 0 (DAY) 0 – 1 Yes Not used by this application.
{30} LAO CURRNT LIMIT 0.1 0
(3)
(3)
Depends on DPI Host product connected to (PowerFlex 70, etc.) and HP size.
0 – 255 No Current limit of the drive. Min value 0.9; max value 6.0
{31} LAO ACCEL TIME 0.1 0
(3)
0 – 32767 No Acceleration time of the drive. Min value 0.1; max
value 3276.7
{32} LAO DECEL TIME 0.1 0
(3)
0 – 32767 No Deceleration time of the drive. Min value 0.1; max
value 3276.7
36 LAO PARAM IN 1 0 0 0 – 32767 No Parameter number to User In point.
{37} LAI USER IN 1 0 0 0 – 32767 Yes User-defined input.
38 LAO PARAM OUT 1 0 0 0 – 32767 No Parameter number to USER IN point.
39 LAO USER OUT 1 0 0 0 – 32767 No User-defined output.
{44} LAI DLNK A1 OUT 1 0 0 0 – 32767 Yes Bits 0-14 of Datalink Out A1.