6-44 Using Explicit Messaging
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
Table 6.W Example Scattered Write COP Response Data
Figure 6.49 Example Scattered Write COP Response Data File
Address
Value
DescriptionHex.
(1)
(1)
In RSLogix 5 software, leading zeros are not displayed in data file addresses. For example, ‘0024’ in address
N30:71 is shown as ‘24’.
Dec.
N30:70 0101 257 TXID = 01, Status = 01 (successful)
N30:71 001E 30 Port = 00, Size = 30 bytes
N30:72 CC01 -13311 Service = CC (successful), Address = 01 (Node)
N30:73 008D 141 Parameter Number (verification)
N30:74 0000 0 Pad Word (0 = successful) or Error Code
N30:75 0000 0 Pad Word = 0 (always zero)
N30:76 008F 143 Parameter Number (verification)
N30:77 0000 0 Pad Word (0 = successful) or Error Code
N30:78 0000 0 Pad Word = 0 (always zero)
N30:79 0069 105 Parameter Number (verification)
N30:80 0000 0 Pad Word (0 = successful) or Error Code
N30:81 0000 0 Pad Word = 0 (always zero)
N30:82 006A 106 Parameter Number (verification)
N30:83 0000 0 Pad Word (0 = successful) or Error Code
N30:84 0000 0 Pad Word = 0 (always zero)
N30:85 006B 107 Parameter Number (verification)
N30:86 0000 0 Pad Word (0 = successful) or Error Code
N30:87 0000 0 Pad Word = 0 (always zero)