Instruction Manual

Using the I/O 5-39
20-COMM-D DeviceNet Adapter User Manual
Publication 20COMM-UM002G-EN-P
Table 5.R SLC 500 Data Table Addresses for:
PowerFlex 700S Drives with Phase II Control
PowerFlex 700L Drives with 700S Control
Data Table Address Description
N9:0 Logic Status (see Appendix
D)
N9:1 Not Used
N9:2 Speed Feedback LSW
N9:3 Speed Feedback MSW
N9:4 Value of parameter assigned to Parameter 660 [DPI Data Out A1] LSW
N9:5 Value of parameter assigned to Parameter 660 [DPI Data Out A1] MSW
N9:6 Value of parameter assigned to Parameter 661 [DPI Data Out A2] LSW
N9:7 Value of parameter assigned to Parameter 661 [DPI Data Out A2] MSW
N9:8 Value of parameter assigned to Parameter 662 [DPI Data Out B1] LSW
N9:9 Value of parameter assigned to Parameter 662 [DPI Data Out B1] MSW
N9:10 Value of parameter assigned to Parameter 663 [DPI Data Out B2] LSW
N9:11 Value of parameter assigned to Parameter 663 [DPI Data Out B2] MSW
N9:12 Value of parameter assigned to Parameter 664 [DPI Data Out C1] LSW
N9:13 Value of parameter assigned to Parameter 664 [DPI Data Out C1] MSW
N9:14 Value of parameter assigned to Parameter 665 [DPI Data Out C2] LSW
N9:15 Value of parameter assigned to Parameter 665 [DPI Data Out C2] MSW
N9:16 Value of parameter assigned to Parameter 666 [DPI Data Out D1] LSW
N9:17 Value of parameter assigned to Parameter 666 [DPI Data Out D1] MSW
N9:18 Value of parameter assigned to Parameter 667 [DPI Data Out D2] LSW
N9:19 Value of parameter assigned to Parameter 667 [DPI Data Out D2] MSW
N10:0 Logic Command (see Appendix
D)
N10:1 Not Used
N10:2 Speed Reference LSW
N10:3 Speed Reference MSW
N10:4 Value of parameter assigned to Parameter 651 [DPI Data In A1] LSW
N10:5 Value of parameter assigned to Parameter 651 [DPI Data In A1] MSW
N10:6 Value of parameter assigned to Parameter 652 [DPI Data In A2] LSW
N10:7 Value of parameter assigned to Parameter 652 [DPI Data In A2] MSW
N10:8 Value of parameter assigned to Parameter 653 [DPI Data In B1] LSW
N10:9 Value of parameter assigned to Parameter 653 [DPI Data In B1] MSW
N10:10 Value of parameter assigned to Parameter 654 [DPI Data In B2] LSW
N10:11 Value of parameter assigned to Parameter 654 [DPI Data In B2] MSW
N10:12 Value of parameter assigned to Parameter 655 [DPI Data In C1] LSW
N10:13 Value of parameter assigned to Parameter 655 [DPI Data In C1] MSW
N10:14 Value of parameter assigned to Parameter 656 [DPI Data In C2] LSW
N10:15 Value of parameter assigned to Parameter 656 [DPI Data In C2] MSW
N10:16 Value of parameter assigned to Parameter 657 [DPI Data In D1] LSW
N10:17 Value of parameter assigned to Parameter 657 [DPI Data In D1] MSW
N10:18 Value of parameter assigned to Parameter 658 [DPI Data In D2] LSW
N10:19 Value of parameter assigned to Parameter 658 [DPI Data In D2] MSW