Manual
60 Rockwell Automation Publication 750COM-UM006A-EN-P - January 2013
Chapter 7 Troubleshooting
SI Events
26 SI Online The option module has logged into the Serial Interface Communications.
27 SI Logon Error The option module failed to log into the Serial Interface.
28 SI Comm Fault The Serial Interface Communications has faulted.
Network Events
29 Net Link Up A network link was available for the option module.
30 Net Link Down The network link was removed from the option module.
31 Net Dup Address The option module uses the same address as another device on the network.
32 Net Comm Fault The option module detected a communications fault on the network.
33 Net Sent Reset The option module received a reset from the network.
34 Net IO Close An I/O connection from the network to the option module was closed.
35 Net Idle Fault The option module received ‘idle’ packets from the network.
36 Net IO Open An I/O connection from the network to the option module has been opened.
37 Net IO Timeout An I/O connection from the network to the option module has timed out.
38 Net IO Size Err The option module received an incorrectly sized I/O packet.
39 PCCC IO Close The device sending PCCC Control messages to the option module has set the PCCC Control Timeout to zero.
40 PCCC IO Open The option module has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a
non-zero value).
41 PCCC IO Timeout The option module has not received a PCCC Control message for longer than the PCCC Control Timeout.
42 Msg Ctrl Open The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing
control messages to be sent to the option module.
43 Msg Ctrl Close The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing control
messages to be sent to the option module.
44 Msg Ctrl Timeout The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.
45 Peer IO Open The option module received the first Peer I/O message.
46 Peer IO Timeout The option module has not received a Peer I/O message for longer than the Peer I/O Timeout.
47-54 Reserved —
55 DHCP Response The option module received a response to its DHCP request.
56 Email Failed The option module encountered an error attempting to send a requested e-mail message.
57 Option Card Flt Internal option module faults.
58 Module Defaulted The option module has been set to defaults.
59 PN WD Timeout A watchdog is detected in the Profinet ASIC.
60 No MAC Addr MAC address has not been assigned, or invalid MAC address.
61 Net Link Up A network link is available at Port 1 of the option module.
62 Net Link Down The network link is removed from Port 1 of the option module.
Table 5 - Option Module Events (Continued)
Code Event Text Description