User Manual
50 Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Chapter 3 Configuring the Option Module
Restoring Option Module
Parameters to Factory
Defaults
As an alternate reset method, you can restore the option module parameters by
using a MEMORY folder menu item instead of using Device Parameter 25 -
[Reset Module] described in Resetting the Option Module on page 49
. The
MEMORY folder method provides two ways to restore the option module
Device and
Host parameters:
• ALL—restores ALL option module Device and Host parameters to their
factory default values.
• MOST—restores MOST option module Device and Host parameters—
except the following which are used for network setup:
– Device Parameter 05 - [Net Addr Sel]
– Device Parameters 07 through 10 - [IP Addr Cfg 1-4]
– Device Parameters 11 through 14 - [Subnet Cfg 1-4]
– Device Parameters 15 through 18 - [Gateway Cfg 1-4]
– Device Parameter 19 - [Net Rate Cfg 1]
– Device Parameter 21 - [Net Rate Cfg 2]
– Device Parameter 23 - [Net Rate Cfg 3] (Tap mode only)
Follow these steps to restore option module Device and Host parameters to their
factory default values.
1. Access the Status screen, which is displayed on HIM powerup.
2. Use the or key to scroll to the Port in which the option
module is installed.
3. Press the key to display its last-viewed folder.
4. Use the or key to scroll to the MEMORY folder.
5. Use the or key to select Set Defaults.
6. Press the (Enter) key to display the Set Defaults pop-up box.
7. Press the (Enter) key again to display the warning pop-up box to
reset Device and Host parameters to their factory default values.
8. Press the MOST soft key to restore MOST Device and Host parameters to
factory defaults or press the ALL soft key to restore ALL parameters. Or
IMPORTANT
When operating the option module in Tap mode, Host parameters are NOT
supported, so only Device parameters are reset to their factory default values.
00
Stopped
0.00 Hz
AUTO
Host Drive
240V 4.2A
Rev 3.002 Ser. A
ESC REF TEXT
F
PAR#