User Manual

Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012 33
Configuring the Option Module Chapter 3
1. Depending on the type of server (BOOTP or DHCP) being used, set
Device Parameter 05 - [Net Addr Sel] to either “2” (BOOTP) or “3”
(DHCP) respectively.
2. Note the option module’s hardware Ethernet Address (MAC), which will
be used in step 7.
There are two ways to do this:
Locate the option module’s hardware Ethernet Address (MAC) on the
module’s product data nameplate label (Figure 8
) located on the
backside of the circuit board.
Figure 8 - Option Module Hardware Address Label Location
Use the HIM to scroll to the drive Port in which the option module is
installed and access the option module’s DIAGNOSTIC folder screen.
Then scroll to Diagnostic Items 49…54 (HW Addr 1…6) to view the
option module’s hardware Ethernet Address (MAC).
3. On a computer connected to the EtherNet/IP network, start the
BOOTP/DHCP software.
Value Setting
1Parameters
2BOOTP
3DHCP (default)
ESC
ENTER
Stopped
0.00 Hz
AUTO
F
▲▼
Edit Net Addr Sel
DHCP 3
1<<3
Ethernet Address (MAC)
label location
Backside of
circuit board