User Manual
138 Rockwell Automation Publication 750COM-UM008A-EN-P - July 2012
Appendix A Specifications
When Operating in Tap Mode
Electrical
Mechanical
Environmental
Regulatory Compliance
NOTE: This is a product of category C2 according to IEC 61800-3. In a
domestic environment this product may cause radio interference in which case
supplementary mitigation measures may be required.
Network
Protocol
Data Rates
EtherNet/IP
10 Mbps Full Duplex, 10 Mbps Half Duplex, 100 Mbps Full Duplex or 100 Mbps
Half Duple
Connection Limits 30 TCP connections
16 simultaneous explicit messaging connections
The following activity uses a CIP connection:
• Explicit messaging where “connected” is chosen (for example, in a checkbox
in RSLogix 5000 software)
The following activity does not
use a CIP connection:
• Explicit messaging where “connected” is NOT chosen, which is typically the
default
Drive
Protocol
Data Rates
DPI
500 kbps
Consumption
Drive
Network
250 mA at 14 VDC supplied by the host drive
None
Dimensions
Height
Length
Width
68 mm (2.7 inches)
150 mm (5.9 inches)
26 mm (1.0 inches)
Weight 62 g (2.1 oz.)
Temperature
Operating
Storage
-10…50 °C (14…122 °F)
-40…85 °C (-40…185 °F)
Relative Humidity 5…95% non-condensing
Atmosphere Important: The option module must not be installed in an area where the
ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the
option module is not going to be installed for a period of time, it must be stored
in an area where it will not be exposed to a corrosive atmosphere.
Certification Specification
UL UL508C
cUL CAN / CSA C22.2 No. 14-2010
CE EN 61800-3
CTick EN 61800-3