37 Net IO Timeout An I/O connection from the network to the option module has timed out.
38 Net IO Size Err The option module received an incorrectly sized I/O packet.
39 PCCC IO Close The device sending PCCC Control messages to the option module has set the PCCC Control Timeout to zero.
40 PCCC IO Open The option module has begun receiving PCCC control messages (the PCCC Control Timeout was previously set to a non-zero value).
41 PCCC IO Timeout The option module has not received a PCCC Control message for longer than the PCCC Control Timeout.
42 Msg Ctrl Open The timeout attribute in either the CIP Register or Assembly object was written with a non-zero value, allowing control messages to be sent to the
option module.
43 Msg Ctrl Close The timeout attribute in either the CIP Register or Assembly object was written with a zero value, disallowing control messages to be sent to the
option module.
44 Msg Ctrl Timeout The timeout attribute in either the CIP Register or Assembly object elapsed between accesses of those objects.
45 Peer IO Open The option module received the first Peer I/O message.
46 Peer IO Timeout The option module has not received a Peer I/O message for longer than the Peer I/O Timeout.
47-54 Reserved —
55 BOOTP Response The option module received a response to its BOOTP request.
56 E-mail Failed The option module encountered an error attempting to send a requested e-mail message.
57 Reserved —
58 Module Defaulted The option module has been set to defaults.
59 FPGA Fact Load The option module has loaded the Factory configuration into its FPGA.
60 FPGA User Load The option module has loaded the User configuration into its FPGA.
61 Net Link 1 Up A network link was available for the option module on its ENET1 network port.
62 Net Link 1 Down The network link was removed from the option module on its ENET1 network port.
63 Net Link 2 Up A network link was available for the option module on its ENET2 network port.
64 Net Link 2 Down The network link was removed from the option module on its ENET2 network port.
65 Net Link 3 Up A network link was available for the option module on its ENET3 (DEVICE) network port.
66 Net Link 3 Down The network link was removed from the option module on its ENET3 (DEVICE) network port.
67 Net Ring Up The Device-Level Ring (DLR) status is Normal.
68 Net Ring Down The Device-Level RIng (DLR) status is Faulted.
69 Invalid Net Cfg The option module’s network address configuration parameters are invalid, or the network address provided by the BOOTP or DHCP server is invalid.
70 DHCP Response The option module received a response to its DHCP request.
71 DHCP Renew The option module renewed its network address lease with the DHCP server.
72 DHCP Rebind The option module rebinded its network address lease with the DHCP server.
73 DHCP Release The option module’s network address lease expired.
Table 12 - Option Module Events (Continued)