100 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Appendix B Option Module Parameters
About Parameter Numbers
Each parameter set is independently and consecutively numbered.
How Parameters Are
Organized
The Device Parameters and Host Parameters are separately displayed in a
Numbered List view order.
Device Parameters
Configuration Tool Numbering Scheme
HIM
Connected Components Workbench software
DriveExplorer software
DriveExecutive software
The Device parameters and Host parameters begin with parameter
01. For example, Device Parameter 01 - [Port Number] and
Host Parameter 01 - [Net to Drv DL 01] are parameter 01 as
indicated by this manual.
Explicit Messaging See Chapter 6
, Using Explicit Messaging and Appendix C,
ControlNet Objects for details.
Parameter
No. Name and Description Details
01 [Port Number]
Displays the drive port into which the option module is installed.
Typically, this will be Port 4, 5, or 6.
Minimum: 4
Maximum: 6
Type: Read Only
02 [DLs From Net Act]
Displays the number of controller-to-drive Datalinks that the
drive is using based on the I/O connection opened by the
controller.
Minimum: 0
Maximum: 16
Type: Read Only
03 [DLs To Net Act]
Displays the number of drive-to-controller Datalinks that the
controller is using based on the I/O connection opened by the
controller.
Minimum: 0
Maximum: 16
Type: Read Only
04 [Net Addr Src]
Displays the source from which the option module node address
is taken. This will be either the Node Address switches (see
Figure 1 on page 18), or the value of Device Parameter 05- [Net
Addr Cfg].
Values: 0 = Switches
1 = Parameters
Type: Read Only
05 [Net Addr Cfg]
Sets the network node address for the option module when
Device Parameter 04 - [Net Addr Src] is set to ‘1’ (Parameters).
Default: 2
Minimum: 1
Maximum: 99
Type: Read/Write
Reset Required: Yes
06 [Net Addr Act]
Displays the actual network node address used by the option
module.
Minimum: 1
Maximum: 99
Type: Read Only