User Manual PowerFlex 20-750-CNETC Coaxial ControlNet Option Module Firmware Revision Number 1.
Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
Summary of Changes This manual contains new and updated information. New and Updated Information This table contains the changes made to this revision. Topic Page Added information about the Connected Components Workbench software configuration tool for drives and connected peripherals. Throughout manual In the Chapter 3 subsection ‘Enable Datalinks To Write Data’, revised step 3 for better understanding.
Summary of Changes Notes: 4 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Table of Contents Preface Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Chapter 1 Getting Started Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Features . . . . . . .
Table of Contents Chapter 5 Using the I/O About I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Understanding the ControlLogix Controller I/O Image. . . . . . . . . . . . . Using Logic Command/Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Using Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Appendix C ControlNet Objects Identity Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Register Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . PCCC Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents Notes: 8 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Preface This manual provides information about the 20-750-CNETC ControlNet option module for network communication and how to use the module with PowerFlex® 750-Series drives. Conventions Used in This Manual The following conventions are used throughout this manual: • Parameter names are shown in the format Device Parameter xx - [*] or Host Parameter xx - [*]. The xx represents the parameter number. The * represents the parameter name—for example Device Parameter 01 - [DPI Port].
Preface Additional Resources These documents contain additional information concerning related products from Rockwell Automation. Resource Description Network Communication Option Module Installation Instructions, publication 750COM-IN002 Information on the installation of PowerFlex 750-Series Network Communication modules.
Chapter 1 Getting Started The 20-750-CNETC option module is intended for installation into a PowerFlex 750-Series drive and is used for network communication. Topic Page Components 11 Features 12 Compatible Products 13 Required Equipment 13 Safety Precautions 15 Quick Start 16 Components ➊ ➋ Part Description ➊ Status Indicators Four status indicators that indicate the status of the option module and network communication. See Chapter 7, Troubleshooting.
Chapter 1 Getting Started Features The features of the option module include the following: • Captive screws to secure and ground the module to the drive. • Switches to set a node address before applying power to the drive—or you can disable the switches and use an option module parameter to configure the node address.
Getting Started Understanding Parameter Types Chapter 1 The option module has two types of parameters: • Device parameters are used to configure the option module to operate on the network. • Host parameters are used to configure the option module Datalink transfer and various fault actions with the drive.
Chapter 1 Getting Started User-Supplied Equipment To install and configure the option module, you must supply the following: ❑ A small screwdriver ❑ ControlNet cable—for details, see the ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002 ❑ Drive and option module configuration tool, such as the following: – PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM – Connected Components Workbench software, version 1.
Getting Started Chapter 1 ❑ Controller configuration software, such as RSLogix 5000 software, version 20.00 or earlier, or Studio 5000™ Logix Designer application, version 21.00 or later ❑ A computer communication card, such as 1784-PCC, 1784-KTCX, or 1770-KFC, for connection to the ControlNet network Safety Precautions Please read the following safety precautions carefully. ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death.
Chapter 1 Getting Started Quick Start 16 This section is provided to help experienced users quickly start using the option module. If you are unsure how to complete a step, refer to the referenced chapter. Step Action See 1 Review the safety precautions for the option module. Throughout this manual 2 Verify that the PowerFlex drive is properly installed. PowerFlex 750-Series AC Drive Installation Instructions, publication 750-IN001 3 Install the option module. a.
Chapter 2 Installing the Option Module This chapter provides instructions for installing the option module in a PowerFlex 750-Series drive.
Chapter 2 Installing the Option Module Setting the Node Address Switches Set the option module Node Address switches (Figure 1) by rotating the switches to the desired value for each digit. IMPORTANT Each node on the ControlNet network must have a unique address. Set the node address before power is applied because the option module uses the node address it detects when it first receives power.
Installing the Option Module Connecting the Option Module to the Drive IMPORTANT Chapter 2 Remove power from the drive before installing the option module in the drive control pod. Install the option module in the PowerFlex 750-Series Drive control pod in Port 4, 5, or 6. For more installation details, see the Network Communication Option Module Installation Instructions, publication 750COM-IN002, provided with the option module.
Chapter 2 Installing the Option Module Applying Power ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive. Apply power to the drive. The option module receives its power from the drive.
Installing the Option Module Chapter 2 Table 1 - Drive and Option Module Start-Up Status Indications Item Name Color State Description Drive STS Indicator ➊ STS (Status) Green Flashing Drive ready but not running, and no faults are present. Steady Drive running, no faults are present. Flashing When running, a type 2 (non-configurable) alarm condition exists – drive continues to run.
Chapter 2 Installing the Option Module The following steps in this section assume that the drive will receive the Logic Command and Reference from the network. 1. Verify that drive Parameter 301 - [Access Level] is set to ‘1’ (Advanced) or ‘2’ (Expert) to access the required parameters in this procedure. 2. Use drive Parameter 545 - [Speed Ref A Sel] to set the drive speed Reference. a. Set the Port field to ‘0’ as shown below. b.
Installing the Option Module Commissioning the Option Module Chapter 2 To commission the option module, you must set a unique network node address. See the Glossary for details about node addresses. When using the Node Address switches, see Setting the Node Address Switches on page 18 for details. IMPORTANT New settings are recognized only when power is applied to the option module or it is reset. After you change parameter settings, cycle power or reset the option module.
Chapter 2 Installing the Option Module Notes: 24 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 3 Configuring the Option Module This chapter provides instructions and information for setting the parameters to configure the option module.
Chapter 3 Configuring the Option Module Using the PowerFlex 20-HIMA6 or 20-HIM-C6S HIM to Access Parameters If your drive has an enhanced PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, it can be used to access parameters in the option module. 1. Display the Status screen, which is shown on HIM power up. 2. Use the or module is installed. key to scroll to the Port in which the option 3. Press the PAR# soft key to display the Jump to Param # entry pop-up box. 4.
Configuring the Option Module Chapter 3 IMPORTANT Always use the Datalink parameters in consecutive numerical order, starting with the first parameter. For example, use Host Parameters 01, 02, and 03 to configure three Datalinks to write data. Otherwise, the network I/O connection will be larger than necessary, which needlessly increases controller response time and memory usage.
Chapter 3 Configuring the Option Module After the above steps are complete, the option module is ready to receive input data and transfer status data to the master (controller). Next, configure the controller to recognize and transmit I/O to the option module. See Chapter 4, Configuring the I/O. Enable Datalinks To Read Data The controller input image (drive-to-controller inputs) can have 0 to 16 additional 32-bit parameters (Datalinks).
Configuring the Option Module Chapter 3 1. Set the values of only the required number of contiguous drive-tocontroller Datalinks needed to read data from the drive and that are to be included in the network I/O connection. 2. Reset the option module; see Resetting the Option Module on page 31. The option module is configured to send output data to the master (controller). You must now configure the controller to recognize and transmit I/O to the option module. See Chapter 4, Configuring the I/O.
Chapter 3 Configuring the Option Module Figure 4 - Edit Fault Action HIM Screens AUTO Stopped F 0.00 Hz Edit Comm Flt Action Fault 0 ESC ▲ 0 << 4 ▼ AUTO Stopped F 0.00 Hz Edit Idle Flt Action Fault 0 ENTER ESC ▲ 0 << 4 ▼ Stopped 0.00 Hz Edit Msg Flt Action Fault 0 ENTER ESC ▲ << 4 ▼ AUTO F 0 ENTER Changes to these parameters take effect immediately. A reset is not required.
Configuring the Option Module Resetting the Option Module Chapter 3 Changes to switch settings and some option module parameters require you to reset the option module before the new settings take effect. You can reset the option module by power cycling the drive or by using Device Parameter 07 [Reset Module]. ATTENTION: Risk of injury or equipment damage exists. If the option module is transmitting control I/O to the drive, the drive may fault when you reset the option module.
Chapter 3 Configuring the Option Module Restoring Option Module Parameters to Factory Defaults As an alternate reset method, you can restore the option module parameters by using a MEMORY folder menu item instead of using Device Parameter 07 [Reset Module] described in Resetting the Option Module on page 31. The MEMORY folder method provides two ways to restore the option module Device and Host parameters: • ALL—restores ALL option module Device and Host parameters to their factory default values.
Configuring the Option Module Viewing the Option Module Status Using Parameters Updating the Option Module Firmware Chapter 3 The following parameters provide information about the status of the option module. You can view these parameters at any time. Module Device Parameter Description 02 - [DLs From Net Act] The number of controller-to-drive Datalinks that are included in the network I/O connection (controller outputs).
Chapter 3 Configuring the Option Module Notes: 34 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 4 Configuring the I/O This chapter provides instructions on how to configure a Rockwell Automation ControlLogix controller to communicate with the option module and connected PowerFlex drive. Using RSLinx Classic Software Topic Page Using RSLinx Classic Software 35 ControlLogix Controller Example 36 RSLinx Classic software, in all its variations (Lite, Gateway, OEM, and so forth), is used to provide a communication link between the computer, network, and controller.
Chapter 4 Configuring the I/O The Configure Drivers dialog box reappears with the new driver in the Configured Drivers list. 8. Click Close to close the Configure Drivers dialog box. 9. Keep RSLinx software running and verify that your computer recognizes the drive. 10. Verify that your computer recognizes the drive. a. From the Communications menu, choose RSWho. b. In the menu tree, click ‘+’ next to the ControlNet driver.
Configuring the I/O Chapter 4 Adding the Bridge to the I/O Configuration To establish communications between the controller and option module over the network, you must first add the ControlLogix controller and its bridge to the I/O configuration. 1. Start RSLogix 5000 software. 2. From the File menu, choose New to display the New Controller dialog box (RSLogix 5000 software, version 16.00 or later shown). a. Choose the appropriate choices for the fields in the dialog box to match your application. b.
Chapter 4 Configuring the I/O In this example, we use a 1756-CNBR ControlNet Bridge (Series D), so the 1756-CNBR/D option is selected. 6. Click OK. 7. In the Select Major Revision pop-up dialog box, select the major revision of its firmware. 8. Click OK. The bridge’s New Module dialog box appears. 9. Edit the following: Box Setting Name A name to identify the ControlNet bridge. Description Optional – description of the ControlNet bridge. Node The node address of the ControlNet bridge.
Configuring the I/O Chapter 4 There are two ways to add the option module into the I/O configuration: • Drive Add-on Profiles (RSLogix 5000 software, version 16.00 or later) • Drive Generic Profile (RSLogix 5000 software, all versions) These are described in the following separate sections. If your version of RSLogix 5000 software supports drive Add-on Profiles, we recommend that you use this method. Using RSLogix 5000 Drive Add-On Profiles, Version 16.
Chapter 4 Configuring the I/O TIP If the PowerFlex drive is not shown, go to http://www.ab.com/support/ abdrives/webupdate and download the latest RSLogix 5000 drive Add-on Profile. 2. From the list, select the drive and its connected option module. For this example, we selected ‘PowerFlex 755-CNETC’. 3. Click OK. The drive’s New Module dialog box appears. 4. On the General tab, edit the following data about the drive/option module. Box Setting Name A name to identify the drive.
Configuring the I/O TIP Chapter 4 To get the latest RSLogix 5000 drive Add-on Profile, go to http://www.ab.comsupport/abdrives/webupdate. 6. In the Module Definition dialog box, edit the following information. Box Setting Revision The major and minor revision of the firmware (database) in the drive. If the drive’s major and minor revision is not available, the drive database is not installed on your computer.
Chapter 4 Configuring the I/O Box Setting Data Format Parameters. When the Connection field is set to ‘Parameters via Datalinks’, ‘Parameters’ is automatically selected. When the Connection field is set to ‘Datalinks’, you must select the number of Datalinks required for your application in the ‘Data Format’ field. Input Data Assigns selected drive or connected peripheral parameters to be READ by the controller using DL To Net Datalinks. See steps 6a through 6e below for details.
Configuring the I/O Chapter 4 b. From the Port field pull-down menu, choose the port of the device to which this Datalink will be assigned (for this example, Port 0, the PowerFlex 755 drive). c. From the Parameter field pull-down menu for the selected device, choose the parameter to which this Datalink will point (for this example, drive parameter 370 - [Stop Mode A]). d. Click OK to complete configuration of the Datalink.
Chapter 4 Configuring the I/O the configuration, these tags allow you to access the Input and Output data of the drive via the controller’s ladder logic.
Configuring the I/O Chapter 4 Figure 7 - Controller Output Tags Save the I/O Configuration to the Controller After adding the bridge and drive/option module to the I/O configuration, you must download the configuration to the controller. You should also save the configuration to a file on your computer. 1. From the Communications menu in the RSLogix 5000 dialog box, choose Download. The Download dialog box appears.
Chapter 4 Configuring the I/O TIP If a message box reports that RSLogix 5000 software is unable to go online, find your controller in the Who Active dialog box. From the Communications menu, choose Who Active. After finding and selecting the controller, click Set Project Path to establish the path. If your controller does not appear, you need to add or configure the ControlNet driver with RSLinx software. See Using RSLinx Classic Software on page 35 and the RSLinx online help for details. 2.
Configuring the I/O Chapter 4 2. Click the Drive tab. 3. Click Connect to Drive to begin the correlation process. After the drive configuration data has been verified, a pop-up dialog box appears, which synchronizes ports from the online drive to the project to be sure that the correct Datalinks are assigned. 4. Click OK. If the Differences Found dialog box appears—which is typical, click Download. This will download the project settings from the controller to the drive and its connected option module.
Chapter 4 Configuring the I/O 6. To match the Datalinks in the drive to the project I/O configuration, click Use Project. After the datalinks have been matched, the Input Data and Output Data columns are grayed out. 7. Click Continue. A series of download dialog boxes appear, which may take a minute to complete. 8. Click OK to close the Module Properties dialog box for the drive. 9.
Configuring the I/O Chapter 4 6. Expand the communication path from your computer to the ControlNet bridge. The following dialog box shows our example navigating to devices on a ControlNet network. Depending on the communication link you are using, the navigation path may be different. 7. Click OK after selecting a valid path to the ControlNet network (for this example, A, ControlNet).
Chapter 4 Configuring the I/O b. On the website search screen in the Network entry field, enter the type of network (for this example, ControlNet), which enables the use of the other search fields. c. In the Keyword entry field, enter the type of PowerFlex 750-Series drive (for this example, PowerFlex 755), noting that this field is space sensitive. d. Click Search. Due to the large number of EDS files, this search may take seconds or up to several minutes. e.
Configuring the I/O Chapter 4 a. Navigate to a folder. b. Type a file name. c. Click Save to save the configuration as a file on your computer. The Save Configuration dialog box appears. d. Click OK to download the I/O configuration to the bridge. TIP When both Save Type choices are available, we recommend to click ‘Optimize and re-write schedule for all connections’.
Chapter 4 Configuring the I/O 2. Expand the Communications group to display all of the available communication modules. 3. Select ‘CONTROLNET-MODULE’ from the list to configure the drive and its connected ControlNet option module. 4. Click OK. The drive’s New Module dialog box appears. 5. Edit the following information about the drive and option module. 52 Box Setting Name A name to identify the drive and option module. Description Optional – description of the drive/option module.
Configuring the I/O Chapter 4 6. Under Connection Parameters, edit the following information. Box Assembly Instance Size Input 1 (This value is required.) The value will vary based on the number of Host [DL From Net xx] parameters used for your application (see details below). Output 2 (This value is required.) The value will vary based on the number of Host [DL To Net xx] parameters used for your application (see details below). Configuration 6 (This value is required.
Chapter 4 Configuring the I/O 9. In the ‘Requested Packet Interval (RPI)’ box, set the value to 5.0 milliseconds or greater (default is 20.0 milliseconds). This value determines the maximum interval that a controller should use to move data to and from the option module. To conserve bandwidth, use higher values for communicating with low priority devices. The ‘Inhibit Module’ box, when checked, inhibits the module from communicating with the RSLogix 5000 project.
Configuring the I/O Chapter 4 Figure 9 - Output Image Controller Tags Save the I/O Configuration to the Controller After adding the bridge and drive/option module to the I/O configuration, you must download the configuration to the controller. You should also save the configuration to a file on your computer. When using RSLogix 5000 software, version 16.00 or later, you can add the I/O configuration of a Generic Profile while the controller is online and in the Run mode. TIP 1.
Chapter 4 Configuring the I/O 2. Click Download to download the configuration to the controller. When the download is successfully completed, RSLogix 5000 software goes into the Online mode and the I/O Not Responding box in the upperleft of the screen should be flashing green. 3. From the File menu, choose Save. If this is the first time you saved the project, the Save As dialog box appears. a. Navigate to a folder. b. Type a file name. c. Click Save to save the configuration as a file on your computer.
Configuring the I/O Chapter 4 6. Expand the communications path from your computer to the ControlNet bridge. The following dialog box shows our example navigating to devices on a ControlNet network. Depending on the communication link you are using, the navigation path may be different. 7. Click OK after selecting a valid path to the ControlNet network (for this example, A, ControlNet).
Chapter 4 Configuring the I/O If the icon for the drive (for this example, PowerFlex 755) on the network appears as Unrecognized Device, you must download the EDS file for that PowerFlex 750-Series drive from the Rockwell AUtomation website. a. Go to the website http://www.rockwellautomation.com/resources/eds. b. On the website search screen in the Network entry field, enter the type of network (for this example, ControlNet), which enables the use of the other search fields. c.
Configuring the I/O Chapter 4 If the bridge has a different I/O configuration than the configuration now being saved, the Online/Offline mismatch dialog box will appear. a. When both Options choices are available, click ‘Use offline data (download)’. When this choice is dimmed (grayed out), you must click ‘Use online data (upload)’. b. Click OK.
Chapter 4 Configuring the I/O Notes: 60 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 5 Using the I/O This chapter provides information and examples that explain how to control, configure, and monitor a PowerFlex 750-Series drive using the configured I/O. Topic Page About I/O Messaging 61 Understanding the ControlLogix Controller I/O Image 62 Using Logic Command/Status 63 Using Reference/Feedback 63 Using Datalinks 64 Example Ladder Logic Program Information 65 ControlLogix Controller Example 66 ATTENTION: Risk of injury or equipment damage exists.
Chapter 5 Using the I/O Understanding the ControlLogix Controller I/O Image The terms ‘input’ and ‘output’ are defined from the controller’s point of view. Therefore, output I/O is data that is produced by the controller and consumed by the option module. Input I/O is status data that is produced by the option module and consumed as input by the controller.
Using the I/O Using Logic Command/Status Chapter 5 The Logic Command is a 32-bit word of control data produced by the controller and consumed by the option module. The Logic Status is a 32-bit word of status data produced by the option module and consumed by the controller. When using a ControlLogix controller, the Logic Command word is always DINT 0 in the output image and the Logic Status word is always: • DINT 0 in the input image when using the drive Add-on Profile.
Chapter 5 Using the I/O When Parameter 300 - [Speed Units] is set to RPM, the other parameters are also in RPM. Table 3 - PowerFlex 750-Series Drive Example Speed Reference/Feedback Scaling Network Reference Value Speed Command Value (2) Output Speed Network Feedback Value 130 Hz 60 Hz (3) 60.0 65.0 65 Hz 60 Hz (3) 60.0 32.5 32.5 Hz 32.5 Hz 32.5 0.0 0 Hz 0 Hz 0.0 -32.5 (1) 32.5 Hz 32.5 Hz 32.5 130.0 (1) The effects of values less than 0.
Using the I/O Chapter 5 anything else that could change the makeup of the I/O connection in a running system. The I/O connection with the controller must first be disabled to allow changes to the respective Datalinks.
Chapter 5 Using the I/O ControlLogix Controller Example This section include information when using a ControlLogix controller and an RSLogix 5000 Drive Add-on Profile or a Generic Profile. Creating Ladder Logic Using the RSLogix 5000 Drive Add-on Profiles, Version 16.
Using the I/O Chapter 5 Figure 11 - ControlLogix Controller Example Ladder Logic Program Using a Drive Add-on Profile for Logic Status/Feedback Figure 12 - ControlLogix Controller Example Ladder Logic Program Using a Drive Add-on Profile for Logic Command/Reference Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012 67
Chapter 5 Using the I/O Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All Versions Option Module Parameter Settings for ControlLogix Controller Example These option module settings were used for the example ladder logic program in this section. Option Module Host Parameter Value Description 01 - [DL From Net 01] 370 Points to drive Par. 370 - [Stop Mode A] 02 - [DL From Net 02] 371 Points to drive Par. 371 - [Stop Mode B] 03 - [DL From Net 03] 535 Points to drive Par.
Using the I/O Chapter 5 Controller Tags When you add the option module and drive to the I/O configuration (Chapter 4), RSLogix 5000 software automatically creates generic (nondescriptive) controller tags. In this example program, the following controller tags are used. You can expand the Input and Output tags to reveal the input and output configuration. The Input tag for this example program requires nineteen 32-bit words of data (see Figure 13).
Chapter 5 Using the I/O Program Tags To use the Controller tags that are automatically created, you need to create the following Program tags for this example program.
Using the I/O Chapter 5 Figure 16 - ControlLogix Controller Example Ladder Logic Program Using a Drive Generic Profile for Logic Command/Reference Example Datalink Data The Datalink data used in the example program is shown in Figure 17. Note that to describe the parameters to which the Datalinks are assigned, you may want to add descriptions to the automatically-created generic controller tags or create a UDDT.
Chapter 5 Using the I/O Figure 17 - ControlLogix Controller Example Datalinks for Ladder Logic Program Using a Drive Generic Profile TIP 72 To determine whether a parameter is a 32-bit integer (DINT) or a REAL data type, see the Data Type column in the chapter containing parameters in the PowerFlex 750-Series AC Drives Programming Manual, publication 750PM001. If a parameter is a REAL, a COP (Copy) instruction or UDDT is needed to copy the DINT to a REAL (inputs) or copy the REAL to a DINT (outputs).
Chapter 6 Using Explicit Messaging This chapter provides information and examples that explain how to use Explicit Messaging with a ControlLogix controller to configure and monitor the option module and connected PowerFlex 750-Series drive. Topic Page About Explicit Messaging 74 Performing Explicit Messaging 75 ControlLogix Controller Examples 76 ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of example.
Chapter 6 Using Explicit Messaging About Explicit Messaging Explicit Messaging is used to transfer data that does not require continuous updates. With Explicit Messaging, you can configure and monitor a slave device’s parameters on the network. IMPORTANT When an explicit message is performed, by default no connection is made since it is an ‘unconnected’ message.
Using Explicit Messaging Performing Explicit Messaging Chapter 6 There are five basic events in the Explicit Messaging process. The details of each step will vary depending on the type of controller being used. See the documentation for your controller. IMPORTANT There must be a request message and a response message for all Explicit Messages, whether you are reading or writing data.
Chapter 6 Using Explicit Messaging ControlLogix Controller Examples To display the Message Configuration dialog box in RSLogix 5000 software, add a message instruction (MSG), create a new tag for the message (Properties: Base tag type, MESSAGE data type, controller scope), and click the button in the message instruction. TIP For supported classes, instances, and attributes, see Appendix C, ControlNet Objects.
Using Explicit Messaging Chapter 6 ControlLogix – Formatting a Message to Read a Single Parameter Figure 20 - Get Attribute Single Message Configuration Dialog Boxes The following table identifies the data that is required in each box to configure a message to read a single parameter. Configuration Tab Example Value Description Message Type Service Type (1) Service Code (1) Class Instance (2) Attribute Source Element Source Length Destination CIP Generic Get Attribute Single e (Hex.) 93 or 9F (Hex.
Chapter 6 Using Explicit Messaging ControlLogix Controller Example Ladder Logic Program to Write a Single Parameter A Set Attribute Single message is used to write to a single parameter. This write message example writes a value to the 32-bit REAL (floating point) parameter 535 - [Accel Time 1] in a PowerFlex 750-Series drive.
Using Explicit Messaging Chapter 6 ControlLogix – Formatting a Message to Write a Single Parameter Figure 22 - Set Attribute Single Message Configuration Dialog Boxes The following table identifies the data that is required in each box to configure a message to write a single parameter. Configuration Tab Example Value Description Message Type Service Type (1) Service Code (1) Class Instance (2) Attribute (3) Source Element Source Length Destination CIP Generic Set Attribute Single 10 (Hex.
Chapter 6 Using Explicit Messaging ControlLogix Controller Example Ladder Logic Program to Read Multiple Parameters A Scattered Read message is used to read the values of multiple parameters.
Using Explicit Messaging Chapter 6 ControlLogix – Formatting a Message to Read Multiple Parameters Figure 24 - Scattered Read Message Configuration Dialog Boxes The following table identifies the data that is required in each box to configure a message to read multiple parameters. Configuration Tab Example Value Description Message Type Service Type (1) Service Code (1) Class Instance Attribute Source Element Source Length Destination CIP Generic Custom 4d (Hex.) 93 or 9F (Hex.) (3) 0 (Dec.) 0 (Hex.
Chapter 6 Using Explicit Messaging ControlLogix Controller Example Scattered Read Request Data In this message example, we use the data structure in Figure 25 in the source tag named Scattered Read Request to read these five 32-bit REAL (floating point) parameters in a PowerFlex 750-Series drive: • Parameter 001 - [Output Frequency] • Parameter 007 - [Output Current] • Parameter 008 - [Output Voltage] • Parameter 009 - [Output Power] • Parameter 011 - [DC Bus Volts] See DPI Parameter Object on page 115 (C
Using Explicit Messaging Chapter 6 ControlLogix Controller Example Ladder Logic Program to Write Multiple Parameters A Scattered Write message is used to write to multiple parameters. This write message example writes the following values to these five 32-bit REAL (floating point) parameters in a PowerFlex 750-Series drive: PowerFlex 750-Series Drive Parameter Write Value 536 - [Accel Time 2] 11.1 Sec 538 - [Decel Time 2] 22.2 Sec 575 - [Preset Speed 5] 33.3 Hz 576 - [Preset Speed 6] 44.
Chapter 6 Using Explicit Messaging ControlLogix – Formatting a Message to Write Multiple Parameters Figure 28 - Scattered Write Multiple Message Configuration Dialog Boxes The following table identifies the data that is required in each box to configure a message to write multiple parameters. Configuration Tab Example Value Description Message Type Service Type (1) Service Code (1) Class Instance Attribute (2) Source Element Source Length Destination CIP Generic Custom 4e (Hex.) 93 or 9F (Hex.
Using Explicit Messaging Chapter 6 ControlLogix Controller Example Scattered Write Request Data In this message example, we use the data structure in Figure 29 in the source tag (Scattered_Write_Request) to write new values to these 32-bit REAL (floating point) parameters: PowerFlex 750-Series Drive Parameter Write Value 536 - [Accel Time 2] 11.1 Sec 538 - [Decel Time 2] 22.2 Sec 575 - [Preset Speed 5] 33.3 Hz 576 - [Preset Speed 6] 44.4 Hz 577 - [Preset Speed 7] 55.
Chapter 6 Using Explicit Messaging ControlLogix Controller – Explanation of Request and Response Data for Read/Write Multiple Messaging The data structures in Table 9 and Table 10 use 32-bit words and can accommodate up to 32 parameters in a single message. In the Response Message, a parameter number with Bit 15 set indicates that the associated parameter value field contains an error code (parameter number in response data will be negative).
Using Explicit Messaging Chapter 6 When performing a Scattered Write to REAL data type parameters, the REAL parameter value will need to be COP to the DINT parameter value tag in the Request (Source Data) array.
Chapter 6 Using Explicit Messaging Notes: 88 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Chapter 7 Troubleshooting This chapter provides information for diagnosing and troubleshooting potential problems with the option module and network. Page Understanding the Status Indicators 89 PORT Status Indicator 90 MOD Status Indicator 90 NET A and NET B Status Indicators 91 Viewing Option Module Diagnostic Items 92 Viewing and Clearing Events 94 The option module has four status indicators. They can be viewed with the drive cover removed.
Chapter 7 Troubleshooting This red/green bicolor LED indicates the status of the option module’s connection to the drive as shown in the table below. PORT Status Indicator Status Cause Corrective Action Off The option module is not powered or is not properly connected to the drive. • Securely connect and ground the option module to the drive by fully inserting it into the drive port and tightening its two captive screws to the recommended torque. • Apply power to the drive.
Troubleshooting Chapter 7 These red/green bicolor LEDs indicate the status for the ControlNet Channel A and Channel B network connections. Depending on the state of these LEDs, they should be interpreted together or independently. NET A and NET B Status Indicators Indicators Interpreted Together When interpreted together, the NET A and NET B LEDs indicate the network status as shown in the table below.
Chapter 7 Troubleshooting If you encounter unexpected communication problems, the option module’s diagnostic items may help you or Rockwell Automation personnel troubleshoot the problem. Option module diagnostic items can be viewed with any of these drive configuration tools: • PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM • Connected Components Workbench software, version 1.02 or later • DriveExplorer software, version 6.01 or later • DriveExecutive software, version 5.
Troubleshooting Chapter 7 Table 11 - Option Module Diagnostic Items (Continued) No. Name Description 27 DL To Net 01 Val 28 DL To Net 02 Val The present value of respective Host DL To Net xx parameter being received from the drive by this option module. (If not using a Datalink, its respective value should be zero.
Chapter 7 Troubleshooting Viewing and Clearing Events The option module has an event queue to record significant events that occur in the operation of the module. When such an event occurs, an entry consisting of the event’s numeric code and a timestamp is put into the event queue. You can view the event queue with any of these drive configuration tools: • PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM • Connected Components Workbench software, version 1.02 or later • DriveExplorer software, version 6.
Troubleshooting Chapter 7 Table 12 - Option Module Events (Continued) Code Event Text Description 13 DPI Baud 125kbps The option module detected that the drive was communicating at 125 Kbps. 14 DPI Baud 500kbps The option module detected that the drive was communicating at 500 Kbps. 15 DPI Host Invalid The option module was connected to an incompatible product. 16 DPI Dup Port Another peripheral with the same port number is already in use.
Chapter 7 Troubleshooting Notes: 96 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Appendix A Specifications This appendix presents the specifications for the option module.
Appendix A Specifications Environmental Regulatory Compliance Temperature Operating Storage -10…50 °C (14…122 °F) -40…85 °C (-40…185 °F) Relative Humidity 5…95% non-condensing Atmosphere Important: The option module must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the option module is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere.
Appendix B Option Module Parameters This appendix provides information about the option module parameters. Parameter Types Topic Page Parameter Types 99 About Parameter Numbers 100 How Parameters Are Organized 100 Device Parameters 100 Host Parameters 101 The Option Module has two types of parameters: • Device parameters are used to configure the option module to operate on the network.
Appendix B Option Module Parameters About Parameter Numbers Each parameter set is independently and consecutively numbered. Configuration Tool Numbering Scheme • • • • The Device parameters and Host parameters begin with parameter 01. For example, Device Parameter 01 - [Port Number] and Host Parameter 01 - [Net to Drv DL 01] are parameter 01 as indicated by this manual.
Option Module Parameters Appendix B Parameter No. Name and Description Details 07 Default: Values: [Reset Module] No action if set to ‘0’ (Ready). Resets the option module if set to ‘1’ (Reset Module). Restores the option module to its factory default settings if set to ‘2’ (Set Defaults). This parameter is a command. It will be reset to ‘0’ (Ready) after the command has been performed.
Appendix B Option Module Parameters Parameter No. Name and Description 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 [DL To Net 01] [DL To Net 02] [DL To Net 03] [DL To Net 04] [DL To Net 05] [DL To Net 06] [DL To Net 07] [DL To Net 08] [DL To Net 09] [DL To Net 10] [DL To Net 11] [DL To Net 12] [DL To Net 13] [DL To Net 14] [DL To Net 15] [DL To Net 16] Sets the port number and parameter number to which the selected Datalinks should connect.
Option Module Parameters Appendix B Parameter No. Name and Description Details 34 Default: Values: [Idle Flt Action] Sets the action that the option module and drive will take if the option module detects that the controller is in program mode or faulted. This setting is effective only if I/O that controls the drive is transmitted through the option module. When the controller is put back in Run mode, the drive will automatically receive commands over the network again.
Appendix B Option Module Parameters Parameter No. Name and Description Details 38 Default: Minimum: Maximum: Type: Reset Required: 0 -3.40282 x 1038 3.
Appendix C ControlNet Objects This appendix presents information about the ControlNet objects that can be accessed using Explicit Messages. For information on the format of Explicit Messages and example ladder logic programs, see Chapter 6, Using Explicit Messaging. Object Class Code Page Hex. Dec. Identity Object 0x01 1 106 Assembly Object 0x05 5 Register Object 0x07 PCCC Object Object Class Code Page Hex. Dec.
Appendix C ControlNet Objects Identity Object Class Code Hexadecimal 0x01 Decimal 1 Services Implemented for: Class Yes Yes Yes Service Code 0x05 0x0E 0x01 Instance Yes Yes Yes Service Name Reset Get_Attribute_Single Get_Attributes_All Instances The number of instances depends on the number of components in the device connected to the option module. This number of components can be read in Instance 0, Attribute 2.
ControlNet Objects Assembly Object Appendix C Class Code Hexadecimal 0x04 Decimal 4 Services Implemented for: Class Instance Yes Yes Yes Yes Service Code 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Instances Instance 1 2 Description All I/O data being read from the DPI device (read-only) All I/O data written to the DPI device (read/write) Class Attributes Attribute ID 1 2 100 Access Rule Get Get Set Name Revision Max Instance Control Timeout Data Type UINT UINT UINT Descri
Appendix C ControlNet Objects Register Object Class Code Hexadecimal 0x07 Decimal 7 Services Service Code Implemented for: Class Instance Yes Yes Yes Yes 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Instances … Description All I/O data being read from the option module (read-only) All I/O data written to the option module (read/write) Logic Status and Feedback data (read-only) Logic Command and Reference data (read/write) DL To Net 01 (input data from option module to scanner)
ControlNet Objects PCCC Object Appendix C Class Code Hexadecimal 0x67 Decimal 103 Services Service Code 0x4B 0x4C Implemented for: Class Instance No Yes No Yes Service Name Execute_PCCC Execute_DH+ Instances Supports Instance 1. Class Attributes Not supported. Instance Attributes Not supported.
Appendix C ControlNet Objects Message Structure for Execute_DH+ Request Name DLink DSta DUser SLink SSta SUser CMD STS TNSW FNC PCCC_params Data Type UINT USINT USINT UINT USINT USINT USINT USINT UINT USINT ARRAY of USINT Description Destination Link ID Destination Station number Destination ‘User’ number Source Link ID Source Station number Source User number Command byte 0 Transport word Function code; not used for all CMDs CMD/FNC specific parameters Response Name DLink DSta DUser SLink SSta SUser C
ControlNet Objects Appendix C N-Files N-File N42 N42:3 N42:7 N42:8 N45 N45:0 N45:1 N45:2 N45:3 N45:4 N45:5 N45:6 N45:7 N45:8 N45:9 N45:10 N45:11 N45:12 N45:13 N45:14 N45:15 N45:16 N45:17 N45:18 N45:19 N45:20 N45:21 N45:22 N45:23 N45:24 N45:25 N45:26 N45:27 N45:28 N45:29 N45:30 N45:31 N45:32 N45:33 N45:34 N45:35 Description This N-file lets you read and write some values configuring the port. Time-out (read/write): Time (in seconds) allowed between messages to the N45 file.
Appendix C ControlNet Objects DPI Device Object Class Code Hexadecimal 0x92 Decimal 146 Services Service Code 0x0E 0x10 Implemented for: Class Instance Yes Yes Yes Yes Service Name Get_Attribute_Single Set_Attribute_Single Instances The number of instances depends on the number of components in the device. The total number of components can be read in Instance 0, Class Attribute 4.
ControlNet Objects Appendix C Class Attributes Attribute ID 0 Access Rule Name Get Family Code Data Type USINT 1 2 Get Set Family Text Language Code STRING[16] USINT 3 Get Product Series USINT 4 Get Number of Components USINT 5 6 7 8 9 11 12 13 Set Get Get Get Get Get Get Get User Definable Text Status Text Configuration Code Configuration Text Brand Code NVS Checksum Class Revision Character Set Code STRING[16] STRING[12] USINT STRING[16] UINT UINT UINT USINT 14 15 Get Get Product Op
Appendix C ControlNet Objects Attribute ID 30 31 Access Rule Name Get International Status Text Get/Set International User Definable Text Data Type STRINGN STRINGN 34 Get STRUCT of: UDINT UDINT UINT UINT UINT USINT USINT USINT USINT USINT USINT[16] UDINT UINT UINT UINT STRING[32] 35 39 128 129 130 Key Information Get Get Get Get Get NVS CRC SI Driver Code Customization Code Customization Revision Number Customization Device Text Description Text describing the status of device with support for U
ControlNet Objects DPI Parameter Object Appendix C Class Code Hexadecimal 0x93 Decimal 147 To access ‘Host Config’ parameters, use the Host DPI Parameter Object (Class Code 0x9F). Instances The number of instances depends on the number of parameters in the device. The total number of parameters can be read in Instance 0, Attribute 0.
Appendix C ControlNet Objects Instance Attributes Attribute ID 6 7 Get DPI Online Read Full 8 9 10 11 Get Get/Set Get/Set Get/Set DPI Descriptor DPI Parameter Value DPI RAM Parameter Value DPI Link 12 13 Get Get Help Object Instance DPI Read Basic 14 15 116 Access Rule Name Get DPI Offline Read Full Get Get DPI Parameter Name DPI Parameter Alias Data Type STRUCT of: BOOL[32] CONTAINER CONTAINER CONTAINER STRING[16] STRING[4] UINT UINT UINT UINT UINT UINT UINT USINT USINT UINT UINT CONTAINER
ControlNet Objects Attribute ID 16 Access Rule Name Data Type Get Parameter Processing Error USINT 18 Get 19 20 21 22 Get Get Get Get International DPI Offline Parameter Text International DPI Online Parameter Text International DPI Online Read Full DPI Extended Descriptor International DPI Offline Read Full Struct of: STRINGN STRINGN Struct of: STRINGN STRINGN Struct of: BOOL[32] CONTAINER CONTAINER CONTAINER CONTAINER UINT UINT UINT UINT UINT INT USINT[3] USINT BOOL[32] STRINGN STRINGN UDINT
Appendix C ControlNet Objects Descriptor Attributes Bit 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 118 Name Data Type (Bit 1) Data Type (Bit 2) Data Type (Bit 3) Description Right bit is least significant bit (0).
ControlNet Objects Appendix C Extended Descriptor Attributes Bit 0 Name Indirect Mode 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Indirect Type 0 Indirect Type 1 Indirect Type 2 Indirect Type 3 Indirect Type 4 Indirect Type 5 Indirect Type 6 Indirect Type 7 Indirect Type 8 Indirect Type 9 Indirect Type 10 Indirect Type 11 Indirect Type 12 Indirect Type 13 Indirect Type 14 FP Max Decimals Bit 0 FP Max Decimals Bit 1 FP Max Decimals Bit 2 FP Max Decimals Bit 1 Extended Parameter Reference 21 22
Appendix C ControlNet Objects Bit 28 Name Description Current Value Is Default This bit identifies a parameter that will not change if a ‘Reset Defaults’ is commanded. For example, if a drive contains a Language parameter that is set to German, setting defaults will leave the parameter set to German. Likewise, if the parameter is set to French, setting defaults will leave the parameter set to French. 29 Use Zero Text If the ‘Disallow Zero’ bit is set, this bit must be cleared.
ControlNet Objects Class Code Hexadecimal 0x97 Decimal 151 Products such as PowerFlex drives use this object for faults. Option modules use this object for events. Services Service Code 0x0E 0x10 Implemented for: Class Instance Yes Yes Yes No Service Name Get_Attribute_Single Set_Attribute_Single Instances The number of instances depends on the maximum number of faults or events supported in the queue. The maximum number of faults/events can be read in Instance 0, Attribute 2.
Appendix C ControlNet Objects Class Attributes Attribute ID 1 2 Access Rule Name Get Class Revision Get Number of Instances Data Type UINT UINT 3 Set Fault Command Write USINT 4 Get Fault Trip Instance Read UINT 5 Get Fault Data List 6 Get Number of Recorded Faults STRUCT of: USINT USINT UINT[n] UINT 7 Get Fault Parameter Reference UINT Description Revision of object Maximum number of faults/events that the device can record in its queue 0 = No Operation 1 = Clear Fault/Event 2 = Cle
ControlNet Objects Class Code Hexadecimal 0x98 Decimal 152 Products such as PowerFlex drives use this object for alarms or warnings. Option modules do not support this object. Services Service Code Implemented for: Class Instance Yes Yes Yes Yes 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Instances Instances (Hex.) (Dec.) 0x0000…0x3FFF 0…16383 Only host devices can have alarms.
Appendix C ControlNet Objects Instance Attributes Attribute ID 0 124 Access Rule Name Get Full/All Information 1 Get Basic Information 2 Get International Alarm Text Data Type STRUCT of UINT STRUCT of: USINT USINT STRING[16] STRUCT of: LWORD BOOL[16] UINT CONTAINER[n] STRUCT of UINT STRUCT of: USINT USINT STRUCT of: LWORD BOOL[16] STRINGN Description Alarm code Alarm source DPI port DPI Device Object Alarm text Alarm time stamp Timer value (0 = timer not supported) BOOL[0]: (0 = invalid data,
ControlNet Objects Class Code Hexadecimal 0x99 Decimal 153 Services Service Code Implemented for: Class Instance Yes Yes Yes Yes 0x0E 0x10 Service Name Get_Attribute_Single Set_Attribute_Single Instances The number of instances depends on the maximum number of diagnostic items in the device. The total number of diagnostic items can be read in Instance 0, Attribute 2.
Appendix C ControlNet Objects Instance Attributes Attribute ID 0 1 2 3 Access Rule Name Get Full/All Information Get/Set Get Get Value International Diagnostic Item Text International Full Read All Data Type STRUCT of: BOOL[32] CONTAINER (1) CONTAINER CONTAINER CONTAINER UINT UINT STRING[4] UINT UINT UINT INT UDINT STRING[16] Various Struct of: STRINGN STRINGN STRUCT of: BOOL[32] CONTAINER CONTAINER CONTAINER CONTAINER UINT UINT UINT UINT UINT INT UDINT BOOL[32] STRINGN STRINGN Description Descrip
ControlNet Objects Appendix C Class Code DPI Time Object Hexadecimal 0x9B Decimal 155 Services Service Code 0x0E 0x10 Implemented for: Class Instance Yes Yes Yes Yes Service Name Get_Attribute_Single Set_Attribute_Single Instances Instances (Hex.) 0x0000…0x3FFF 0x4000…0x43FF Device Example Description (Dec.
Appendix C ControlNet Objects Attribute ID 8 9 Access Rule Name Get Active Time Zone Data Get/Set Custom Time Zone Data Data Type Struct of: INT USINT USINT USINT USINT USINT USINT INT USINT USINT USINT USINT USINT USINT Struct of: INT USINT USINT USINT USINT USINT USINT INT USINT USINT USINT USINT USINT USINT Description Standard bias Standard month Standard day of week Standard week Standard hour Standard minute Standard second Daylight offset Daylight month Daylight day of week Daylight week Dayl
ControlNet Objects Host DPI Parameter Object Appendix C Class Code Hexadecimal 0x9F Decimal 159 To access ‘Device’ parameters, use the DPI Parameter Object (Class Code 0x93). Instances The number of instances depends on the number of parameters in the device. The total number of parameters can be read in Instance 0, Attribute 0.
Appendix C ControlNet Objects Instance Attributes Attribute ID 6 7 Get DPI Online Read Full 8 9 10 11 Get Get/Set Get/Set Get/Set DPI Descriptor DPI Parameter Value DPI RAM Parameter Value DPI Link 12 13 Get Get Help Object Instance DPI Read Basic 14 15 130 Access Rule Name Get DPI Offline Read Full Get Get DPI Parameter Name DPI Parameter Alias Data Type STRUCT of: BOOL[32] CONTAINER CONTAINER CONTAINER STRING[16] STRING[4] UINT UINT UINT UINT UINT UINT UINT USINT USINT UINT UINT CONTAINER
ControlNet Objects Attribute ID 16 Access Rule Name Data Type Get Parameter Processing Error USINT 18 Get 19 20 21 22 Get Get Get Get International DPI Offline Parameter Text International DPI Online Parameter Text International DPI Online Read Full DPI Extended Descriptor International DPI Offline Read Full Struct of: STRINGN STRINGN Struct of: STRINGN STRINGN Struct of: BOOL[32] CONTAINER CONTAINER CONTAINER CONTAINER UINT UINT UINT UINT UINT INT USINT[3] USINT BOOL[32] STRINGN STRINGN UDINT
Appendix C ControlNet Objects Descriptor Attributes 132 Bit 0 1 2 Name Data Type (Bit 1) Data Type (Bit 2) Data Type (Bit 3) 3 Sign Type 4 Hidden 5 Not a Link Sink 6 Not Recallable 7 ENUM 8 Writable 9 Not Writable When Enabled 10 Instance 11 12 13 14 15 16 17 18 Uses Bit ENUM Mask Decimal Place (Bit 0) Decimal Place (Bit 1) Decimal Place (Bit 2) Decimal Place (Bit 3) Extended Data Type (Bit 4) Extended Data Type (Bit 5) Extended Data Type (Bit 6) 19 20 21 22 23 24 25 26 Parameter Ex
ControlNet Objects Appendix C Extended Descriptor Attributes Bit 0 Name Indirect Mode 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Indirect Type 0 Indirect Type 1 Indirect Type 2 Indirect Type 3 Indirect Type 4 Indirect Type 5 Indirect Type 6 Indirect Type 7 Indirect Type 8 Indirect Type 9 Indirect Type 10 Indirect Type 11 Indirect Type 12 Indirect Type 13 Indirect Type 14 FP Max Decimals Bit 0 FP Max Decimals Bit 1 FP Max Decimals Bit 2 FP Max Decimals Bit 1 Extended Parameter Reference 0 = Not
Appendix C ControlNet Objects Bit 28 Name Current Value Is Default 29 Use Zero Text Description This bit identifies a parameter that will not change if a ‘Reset Defaults’ is commanded. For example, if a drive contains a Language parameter that is set to German, setting defaults will leave the parameter set to German. Likewise, if the parameter is set to French, setting defaults will leave the parameter set to French. If the ‘Disallow Zero’ bit is set, this bit must be cleared.
Appendix D Logic Command/Status Words: PowerFlex 750-Series Drives This appendix presents the definitions of the Logic Command and Logic Status words that are used for PowerFlex 750-Series drives.
Appendix D Logic Command/Status Words: PowerFlex 750-Series Drives Logic Status Word Logic Bits 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 x x x x x x x x x x x x x x x x x x x x x Active Command Direction Actual Direction Accelerating Decelerating Alarm Fault At Setpt Spd Manual Spd Ref ID 0 Spd Ref ID 1 Spd Ref ID 2 Spd Ref ID 3 Spd Ref ID 4 Reserved Running Jogging Stopping DC Brake DB Active Speed Mode x Position Mode x Torque Mode x At Zero S
Appendix E History of Changes Topic Page 750COM-UM003A-EN-P, September 2009 137 This appendix summarizes the revisions to this manual. Reference this appendix if you need information to determine what changes have been made across multiple revisions. This may be especially useful if you are deciding to upgrade your hardware or software based on information added with previous revisions of this manual. 750COM-UM003A-EN-P, September 2009 Change This was the first release of this manual.
Appendix E History of Changes Notes: 138 Rockwell Automation Publication 750COM-UM001E-EN-P - March 2013
Glossary The following terms and abbreviations are used throughout this manual. For definitions of terms not listed here, see the Allen-Bradley Industrial Automation Glossary, publication AG-7.1. Bridge A network device that can route messages from one network to another. A bridge also refers to a communication module in a ControlLogix controller that connects the controller to a network. See also scanner.
Glossary DriveExplorer Software A tool for monitoring and configuring Allen-Bradley products and network communication adapters. It can be used on computers running various Microsoft Windows operating systems. DriveExplorer software, version 6.xx or later, can be used to configure this adapter and connected drive. This software tool has been discontinued and is now available as freeware at http://www.ab.com/support/ abdrives/webupdate/software.html.
Glossary Idle Action An idle action determines how the option module and connected drive act when the controller is switched out of run mode. I/O Data I/O data, sometimes called ‘implicit messages’ or ‘input/output’, is time-critical data such as a Logic Command and Reference. The terms ‘input’ (To Net) and ‘output’ (From Net) are defined from the controller’s point of view. Output is produced by the controller and consumed by the option module.
Glossary Ping A message that is sent on the network to determine if a node exists. PowerFlex 750-Series (Architecture Allen-Bradley PowerFlex 750-Series drives are part of the PowerFlex 7-Class Class) Drives family of drives. Producer/Consumer Network On producer/consumer networks, packets are identified by content rather than an explicit destination. If a node needs the packet, it will accept the identifier and consume the packet.
Glossary Studio 5000 Environment The Studio 5000 Engineering and Design Environment combines engineering and design elements into a common environment. The first element in the Studio 5000 environment is the Logix Designer application. The Logix Designer application is the rebranding of RSLogix 5000 software and will continue to be the product to program Logix 5000 controllers for discrete, process, batch, motion, safety, and drive-based solutions.
Glossary Notes: 144 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Index A applying power to the option module 20 Assembly object 107 attentions 15 B baud rate, see data rate bit definitions of Logic Command/Status word for PowerFlex 750-Series drives 135 bridge 139 C cable, ControlNet 19 CIP (Common Industrial Protocol) 139 Comm Flt Action Host parameter 102 commissioning the option module 23 communications card, see option module compatible products description 13 documentation for 10 components of the option module 11 configuration tools 25 Connected Components Workbe
Index hold last configuring the option module for 29 definition 140 Host DPI Parameter object 129 Host parameters list 101-104 I I/O about 61 configuring for ControlLogix controller 36 configuring/saving to ControlLogix controller using RSNetWorx for ControlNet software 48, 56 definition 141 understanding the I/O image 62 using with ControlLogix controller 66 Identity object 106 idle action 141 Idle Flt Action Host parameter 103 installation applying power to the option module 20 commissioning the option
Index PowerFlex 750-Series (Architecture Class) drives compatible with option module 13 definition 142 HIM 26 preparing for an installation 17 processor, see controller producer/consumer network 142 programmable logic controller, see controller status indicators definition 142 MOD 89, 90 NET A 89, 91 NET B 89, 91 normal operation 20 PORT 89, 90 troubleshooting with 90-91 understanding 89 stop action 142 Studio 5000 environment 143 Q T quick start 16 R Reference/Feedback definition 142 in I/O image for
Index Notes: 148 Rockwell Automation Publication 750COM-UM003B-EN-P - November 2012
Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.