Manual
24 Rockwell Automation Publication 750-UM003B-EN-P - July 2013
Chapter 2 Installation and Wiring
4. Firmly press the 11-Series I/O option module edge connector into port 4
or port 5.
5. Tighten the top and bottom retaining screws:
• Recommended torque = 0.45 N•m (4.0 lb•in)
• Recommended screwdriver = T15 Hexalobular
IMPORTANT
The ATEX option module mounted on an 11-Series I/O option module
can be installed only in drive ports 4 or 5.
IMPORTANT
Do not over-tighten the retaining screws.