Chapter 2 Installation and Wiring
Connect the Thermal Sensor
Wires
Connect the thermal sensor wires to the removable terminal block of the ATEX
option module.
Table 2 - ATEX Terminal Designations
Cabling Requirements
Follow these requirements for thermal sensor wiring to the removable terminal
block of the ATEX option module:
Use cable ducting, conduit, armored cable, or other means to protect the
thermal sensor wires from damage.
Use shielded, twisted-pair cable.
Installation Requirements
Installation must meet the radio frequency (RF) emission compliance and
installation requirements outlined in the PowerFlex 750-Series AC Drives
Installation Instructions, publication 750-IN001
.
20-750-ATEX
Terminal Name Description Related
Parameter
ATEX+ ATEX input (+) Motor protection device input.
Thermostat or PTC-type device.
Polarity can be ignored.
Parameter 41
[ATEX Sts]
See Parameter 41
[ATEX Sts] on
page 33.
ATEX- ATEX input ()
ATEX+
ATEX-
2
1