User Manual

DeviceNet Information A-21
Publication 198-UM001B-EN-P September 2001
25 Get I/O Error USINT 0 = No error
1 = Module added
2 = Module removed
3 = Module different
4 = Invalid ID
5 = Invalid module configuration
6 = Too many modules
7 = CSum error count for error > 500
8 = Unused
9 = EEprom failure
10 = Unable to power bus
11 = Sensor or valve voltage error
12 = Overcurrent
13 = Short-term overtemp
14 = Long-term overtemp
26 Get Error Location UINT 0 = Module (X) OK
1 = Fault detected at module (X)
Bit 0 = Module 1
:
Bit 15 = Module 16
27 Get/Set Accept
Configuration
BOOL 0 -> 1 Save new module config to EEprom
28 Get CSum Count UINT Number of CSum errors reported on the
module bus
Number increases by 3 upon an error
message and decreases by 1 upon a good
message
29
Get Module Error
Number
BYTE 0= No modules
1= Module 1
2 = Module 2
3 = Module 3
16 = Module 16
30 Get Dnet Voltage UINT 0…65535 mV
31 Get Module Bus
Voltage
UINT 0…65535 mV
32 Get I/O Bus Current UINT 0…19168 mA (course reading with 18 mA
resolution)
33 Get Number of
Modules
USINT Number of Modules Attached
34 Get Module ID Slot 1 USINT
35 Get Module ID Slot 2 USINT
36 Get Module ID Slot 3 USINT
37 Get Module ID Slot 4 USINT
38 Get Module ID Slot 5 USINT
39 Get Module ID Slot 6 USINT
40 Get Module ID Slot 7 USINT
41 Get Module ID Slot 8 USINT
42 Get Module ID Slot 9 USINT
43 Get Module ID Slot 10 USINT
44 Get Module ID Slot 11 USINT
Table A.33 DeviceNet Interface Object Instance Attributes (Continued)
Attribute
ID
Access
Rule
Name Data Type Value