User Manual
A-14 DeviceNet Information
Publication 198-UM001B-EN-P September 2001
Input Assembly Instance 107
This assembly reserves a byte (8 bits) for every module on the system — regardless of
whether it has any inputs. The size of the assembly 20 bytes — four for status and 16 for data.
This is the default assembly for 198-DN module. The following is a generalization of the
input assembly instance. The status and error codes follow on pages A-15 and A-16.
Table A.19 Input Assembly Instance 107
Slot Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Module
Status 8
Module
Status 7
Module
Status 6
Module
Status 5
Module
Status 4
Module
Status 3
Module
Status 2
Module
Status 1
1 Module
Status
16
Module
Status
15
Module
Status
14
Module
Status
13
Module
Status
12
Module
Status
11
Module
Status
10
Module
Status 9
2 Module Error Number
3 Error Code
1 4——————Input 2Input 1
2 5——————Input 2Input 1
3 6 — — — — Open Short Input 2 Input 1
4 7————————
5 8——————Input 2Input 1
6 9——————Input 2Input 1
7 10————————
8 11————————
9 12————————
1013————————
1114————————
1215————————
1316————————
1417————————
1518————————
1619————————