User Manual
5-56 Specifications
Publication 198-UM001B-EN-P September 2001
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
➊
When wired as shown in the following diagrams. Typical in a Distributed Starter. Input 1 represents the
disconnect status. Input 2 represents the fault status of the 160 drive.
Table 5.AE 198-IB2XOB5S I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
——————Input2
➊
Input 1
➊
Input Data — Assembly Instance 101
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
——Input2
➊
Input 1
➊
Output Data — Assembly Instance 100, 102, 104, or 106
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
— Speed 3 Speed 2 Speed 1 — — Run Reverse Run Forward
Drive Control
➊
Run
Reverse
Run
Forward
Drive
Control
Run
Reverse
Run
Forward
Drive
Control
00Stop 10Run Reverse
01Run Forward 11Stop
Output Data Speed Settings
➊
Speed 3 Speed 2 Speed 1 Setting Speed 3 Speed 2 Speed 1 Setting
000Speed
Setting 1
100 Speed
Setting 5
001Speed
Setting 2
101 Speed
Setting 6
010Speed
Setting 3
110 Speed
Setting 7
011Speed
Setting 4
111 Speed
Setting 8