Specifications 5-49
Publication 198-UM001B-EN-P September 2001
Assembly Instances 104 and 105 are default for 198-DNG. Assembly Instances 106 and 107
are default for 198-DN.
In a typical Distributed Starter, Input 1 represents the disconnect status. Input 2 represents the contactor
status. If this bit is set, the disconnect or contactor is closed. If this bit is not set, the disconnect or contactor
is open.
Figure 5.35 Cat. No. 198-IB2XOW1 Typical Wiring
Table 5.AC 198-IB2XOW1 I/O Produced/Consumed Data
Input Data — Assembly Instance 103, 105, or 107
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
——————Input2
Input 1
Input Data — Assembly Instance 101
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
——Input1
Input 1
Output Data — Assembly Instance 102, 104, or 106
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
——————— Output1
Output Data — Assembly Instance 100
Bit 3 or 7 Bit 2 or 6 Bit 1 or 5 Bit 0 or 4
———Output1
120/240V ac
IN1
Out A
N
N
DC
DC
IN2
L
(
+V
)
+Vout
IN1
IN2
Out A
N
N
L
120/240V AC
DC
DC
Typical Wiring Series A Typical Wiring Series B