User Manual
Publication 193-UM010A-EN-P – January 2008
A-2 Specifications
Type of Inputs Current Sinking
ON-State Voltage 15V DC
On-State Current (turn-on) 15 mA
Steady State Current 15 mA
Off-State Voltage 5 VDC
Off-State Current 0.5 mA
Transition Voltage 5... 15 VDC
Transition Current 0.5... 15mA
Environmental Ratings:
Ambient Temperature Tamb
Storage
Operating
(Open)
(Enclosed)
-40…+85°C (-40…+185°F)
-20…+60°C (-4…+140°F)
-20…+40°C (-4…+104°F)
Humidity
Operating
Damp Heat - Steady State
Damp Heat - Cyclic
5…95% non-condensing
per IEC 68-2-3
per IEC 68-2-30
Cooling Method Natural Convection
Vibration (per IEC 68-2-6) 3 G
Shock (per IEC 68-2-27) 30 G
Maximum Altitude 2000 m
Pollution Environment Pollution Degree 2
Terminal Marking EN 50012
Degree of Protection IP20
Electromagnetic Compatibility
Electrostatic Discharge Immunity
Test Level
Performance Criteria
8 kV Air Discharge
4 kV Contact Discharge
1
(1)(2)
Radiated RF Immunity
Test Level
Performance Criteria
10V/m
1
(1)(2)
Electrical Fast Transient/Burst Immunity
Test Level
Performance Criteria
2 kV (Power)
1 kV (control)
1
(1)(2)
Surge Immunity
Test Level
Performance Criteria
2 kV L-E
1 kV L-L
1
(1)(2)
Radiated Emissions Class A
Conducted Emissions Not tested
WARNING
This is a class A product. In domestic environment, this product may cause radio interference, in which case the
user may be required to take adequate measures.
PROFIBUS Communications:
Baud Rate 9.6 k, 19.2 k, 45.45 k, 93.75 k,
187.5 k, 500 k, 1.5 M, 3 M, 6 M,
12 M
Auto-Baud Rate identification Yes