User Manual

Publication 193-UM010A-EN-P – January 2008
PROFIBUS Configuration 3-11
Trip History Group
OutA Pb IdlValue Index No. 27
This parameter determines the state that Output A assumes
when the network is idle and parameter 26 is set to “0”.
Access Rule Read/Write
Size 1 byte
Group I/O Setup
Units
Min. Value 0 = Open
Max. Value 1 = Closed
Default Value 0
IN1 Assignment Index No. 28
This parameter allows the user to assign a specific function
to the discrete IN1 input.
Access Rule Read/Write
Size 1 byte
Group I/O Setup
Units
Min. Value
Max. Value
0 = Normal
1 = Trip reset
2 = OL Contact
Default Value 0
IN2 Assignment Index No. 29
This parameter allows the user to assign a specific function
to the discrete IN2 inputs.
Access Rule Read/Write
Size 1 byte
Group I/O Setup
Units
Min. Value
Max Value
0 = Normal
1 = Trip Reset
2 = OL Contact
Default Value 0
Trip Log 0 Index No. 30
This parameter records the latest trip. Access Rule Read
Size 2 byte
Group Trip History
Units
Min. Value See Trip Status table
Max. Value See Trip Status table
Default Value None
Trip Log 1 Index No. 31
This parameter records the trip previous to Trip Log 0. Access Rule Read
Size 2 bytes
Group Trip History
Units
Min. Value See Trip Status table
Max. Value See Trip Status table
Default Value None