User Manual
Publication 193-UM010A-EN-P – January 2008
PROFIBUS Configuration 3-9
Reset/Lock Group
UL Warn Level Index No. 18
This parameter sets the underload warning level. Access Rule Read/Write
Size 1 byte
Group Advanced Setup
Units % FLA
Min. Value 30
Max. Value 100
Default Value 70
Trip Reset Index No. 19
This parameter provides the user with the capability of
resetting a trip over the PROFIBUS network. After a trip is
reset, the parameter automatically returns to a “Ready”
state.
Access Rule Read/Write
Size 1 byte
Group Reset/Lock
Units —
Min. Value 0 = Ready
Max. Value 1 = Reset Trip
Default Value 0
Program Lock Index No. 20
This parameter prohibits the device parameters from being
altered when set to “Locked”. It must be set to “Unlocked”
to allow parameter modification.
Access Rule Read/Set
Size 1 byte
Group Reset/Lock
Units —
Min. Value 0 = Unlocked
Max. Value 1 = Locked
Default Value 0
Set To Defaults Index No. 21
This parameter allows the user to reset the parameter
settings to the factory default values. After parameter
values have been reset to the factory default settings, the
parameter automatically returns to a “Ready” state.
Access Rule Read/Write
Size 1 byte
Group Reset/Lock
Units —
Min. Value 0 = Ready
Max. Value 1 = Reset Defaults
Default Value 0