3-8 PROFIBUS Configuration
Jam Inhibit Time Index No. 13
This parameter defines the amount of time for which jam
detection is inhibited during a motor starting sequence.
Access Rule Read/Write
Size 1 byte
Group Advanced Setup
Units Seconds
Min. Value 0
Max. Value 250
Default Value 10
Jam Trip Delay Index No. 14
This parameter allows the installer to program a time
duration for which a jam condition must exist at the
programmed level prior to the device tripping.
Access Rule Read/Write
Size 1 byte
Group Advanced Setup
Units Seconds
Min. Value 0.5
Max. Value 25.0
Default Value 5.0
Jam Trip Level Index No. 15
This parameter sets the jam trip level. Access Rule Read/Write
Size 2 bytes
Group Advanced Setup
Units % FLA
Min. Value 150
Max. Value 600
Default Value 250
Jam Warn Level Index No. 16
This parameter sets the jam warning level. Access Rule Read/Write
Size 2 bytes
Group Advanced Setup
Units % FLA
Min. Value 100
Max. Value 600
Default Value 150
UL Inhibit Time Index No. 17
This parameter defines the amount of time for which
underload detection is inhibited during a motor starting
sequence.
Access Rule Read/Write
Size 1 byte
Group Advanced Setup
Units Seconds
Min. Value 0
Max. Value 250
Default Value 10