3-6 PROFIBUS Configuration
Advanced Setup Group
Bit Function:
1514131211109876543210
XTrip
X Warning
XOut A
XIn 1
XIn 2
X Motor Current
XXXXXXXXXX Not Used
Firmware Revision Index No. 6
This parameter reports the firmware revision of the PROFIBUS
Module.
Format:
0x0107 equals version 1.07
Access Rule Read
Size 2 bytes
Group Monitor
Units
Min. Value 0
Max. Value 65535
Default Value None
Serial Number Index No. 7
This parameter reports the serial number assigned during
production of the PROFIBUS Module.
Access Rule Read
Size 4 bytes
Group Monitor
Units
Min. Value 0
Max. Value 0xFFFFFFFF
Default Value None
Trip Enable Index No. 8
This parameter allows the installer to enable or
disable the Jam Trip function
1 = Enabled
0 = Disabled
Access Rule Read/Write
Size 2 bytes
Group Advanced Setup
Units
Min. Value 0000000000000000
Max. Value 0000000000000100
Default Value 0000000000000000
Bit Function:
1514131211109876543210
X Not Used
X Not Used
X Jam
XXXXXXXXXXXXX Not Used