PROFIBUS Configuration 3-5
Trip Status Index No. 3
This parameter provides trip identification.
1 = Trip
0 = No Trip
Access Rule Read
Size 2 bytes
Group Monitor
Units —
Min. Value —
Max. Value —
Default Value None
Bit Function:
1514131211109876543210
X Overload
X Phase Loss
X Jam
XXXXXXXXXXXXX Not Used
Warning Status Index No. 4
This parameter provides warning identification
1 = Warning
0 = No Warning
Access Rule Read
Size 2 bytes
Group Monitor
Units —
Min. Value —
Max. Value —
Default Value None
Bit Function:
1514131211109876543210
X Overload
XNot Used
X Jam
X Underload
XNot Used
X Comm Fault
X Comm Idle
X Nonvolatile Memory Fault
XXXXXXXX Not Used
Device Status Index No. 5
This parameter provides status information related to the E1
Plus Overload Relay and the PROFIBUS Module.
1 = On or Present
0 = Off or Not Present
Access Rule Read
Size 2 bytes
Group Monitor
Units —
Min. Value —
Max. Value —
Default Value None