Owner manual
Publication 193-UM006A-EN-P – October 2005
DeviceNet Information B-15
The following common services are implemented for the Control Supervisor
Object:
104 Get Trip Log 2 WORD Last trip condition. Bit definitions of the value are the same as
attribute 114.
105 GEt Trip Log 3 WORD Last trip condition. Bit definitions of the value are the same as
attribute 114.
106 Get Trip Log 4 WORD Last trip condition. Bit definitions of the value are the same as
attribute 114.
107 Get Device Status WORD Bit 0=Trip
Bit 1=Warning
Bit 2=OutputA
Bit 3=Input 1
Bit 4=Input 2
BIt 5=Motor Current
108 Get/Set Trip Enable WORD Bit 0=Not Used
Bit 1=Not Used
Bit 2=Jam
Bit 3=Not Used
Bit 4=Not Used
BIt 5=Not Used
Bit 6=Not Used
Bit 7=Not Used
109 Get/Set Warning Enable WORD Bit 0=Overload
Bit 1=Not Used
Bit 2=Jam
Bit 3=Underload
Bit 4=Not Used
BIt 5=Comm Fault
Bit 6=Comm Idle
Bit 7=Not Used
110 Get/Set Reset Mode BOOL 0=Manual
1=Automatic
111 Get/Set IN1 Assignment USINT 0=Normal
1=Trip Rest
2=OL Contact
112 Get/Set IN2 Assignment USINT 0=Normal
1=Trip Reset
2=OL Contact
Table B.35 Control Supervisor Object Instance Attributes
Attribute
ID
Access Rule Name Data Type Value
Table B.36 Control Supervisor Object Common Services
Service
Code
Implemented for:
Service Name
Class Instance
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single