4-12 Device Parameters
I/O Setup Group
OutA Pr FltState Parameter No. 34
This parameter, in conjunction with
parameter 35, defines how Output A will
respond when a trip occurs. When set to “1”,
Output A will continue to operate as
commanded via the network. When set to
“0”, Output A will open or close as
determined by the setting of parameter 35.
Access Rule Get/Set
Data Type BOOL
Group I/O Setup
Units —
Min. Value 0 = Go To FltValue (#35)
Max. Value 1 = Ignore Fault
Default Value 0
OutA Pr FltValue Parameter No. 35
This parameter determines the state that Output
A assumes when a trip occurs and Parameter 34
is set to “0”.
Access Rule Get/Set
Data Type BOOL
Group I/O Setup
Units —
Min. Value 0 = Open
Max. Value 1 = closed
Default Value 0
OutA DN FltState Parameter No. 36
This parameter, in conjunction with
Parameter 37, defines how Output A will
respond when a DeviceNet network fault
occurs. When set to “1”, Output A will hold
the state prior to trip occurrence. When set
to “0”, Output A will open or close as
determined by the setting of Parameter 37.
Access Rule Get/Set
Data Type BOOL
Group I/O Setup
Units —
Min. Value 0 = Go To FltValue (#37)
Max. Value 1 = Hold Last State
Default Value 0
OutA DN FltValue Parameter No. 37
THis parameter determines the state that
Output A assumes when a DeviceNet network
fault occurs and Parameter 36 is set to “0”.
Access Rule Get/Set
Data Type BOOL
Group I/O Setup
Units —
Min. Value 0 = Open
Max. Value 1 = Closed
Default Value 0