4-10 Device Parameters
DeviceNet Setup Group
AutoBaudEnable Parameter No. 26
When this parameter is enabled, the device will
attempt to determine the network baud rate and
set its baud rate to the same, provided network
traffic exists. At least one node with an
established baud rate must exist on the network
for autobaud to occur.
Access Rule Get/Set
Data Type BOOL
Group DeviceNet Setup
Units —
Min. Value 0 = Disabled
Max. Value 1 = Enabled
Default Value 1
NonVol Baud Rate Parameter No. 27
This parameter allows monitoring of the
communication rate setting as determined in the
node commissioning tool.
Access Rule Get
Data Type USINT
Group DeviceNet Setup
Units —
Min. Value
Max. Value
0 = 125k
1 = 250k
2 = 500k
Default Value 0
Output Assembly Parameter No. 28
This parameter is used to select the desired
Output Assembly. See Appendix B—DeviceNet
Information for a listing of available assemblies.
Access Rule Get/Set
Data Type USINT
Group DeviceNet Setup
Units —
Min. Value 0
Max. Value 103
Default Value 103
Input Assembly Parameter No. 29
This parameter is used to select the desired
Input Assembly. See Appendix B—DeviceNet
Information for a listing of available assemblies.
Access Rule Get/Set
Data Type USINT
Group DeviceNet Setup
Units —
Min. Value 0
Max. Value 110
Default Value 110