Device Parameters 4-7
OL Reset Mode Parameter No. 16
This parameter defines whether a trip can be
automatically or manually reset. This setting
overrides the E1 Plus DIP switch adjustment
while the DeviceNet Module is powered. Note,
however, that the E1 Plus manual reset button,
accessible at the front, is always active.
Access Rule Get/Set
Data Type BOOL
Group Advanced Setup
Units —
Min. Value 0 = Manual
Max. Value 1 = Automatic
Default Value 0
OL Warning Level Parameter No. 17
This parameter sets the overload warning level. Access Rule Get/Set
Data Type USINT
Group Advanced Setup
Units % Thermal
Utilization
Min. Value 0
Max. Value 100
Default Value 90
Jam Inhibit Time Parameter No. 18
This parameter defines the amount of time for
which jam detection is inhibited during a motor
starting sequence.
Access Rule Get/Set
Data Type USINT
Group Advanced Setup
Units Seconds
Min. Value 0
Max. Value 250
Default Value 10
Jam Trip Delay Parameter No. 19
This parameter allows the installer to program a
time duration for which a jam condition must
exist at the programmed level prior to the device
tripping.
Access Rule Get/Set
Data Type USINT
Group Advanced Setup
Units Seconds
Min. Value 0.5
Max. Value 25.0
Default Value 5.0