Owner manual
Publication 193-UM006A-EN-P – October 2005
4-6 Device Parameters
Bit Function:
1514131211109876543210
X Not Used
X Not Used
X Jam
XXXXXXXXXXXXX Not Used
Warning Enable Parameter No. 13
This parameter allows the installer to enable or
disable the warning functions separately. All
warning functions are disabled from the factory.
1 = Enabled
0 = Disabled
Access Rule Get/Set
Data Type WORD
Group Advanced Setup
Units —
Min. Value 0000000000000000
Max. Value 0000000001101101
Default Value 0000000000000000
Bit Function:
1514131211109876543210
X Overload
X Not Used
X Jam
X Underload
X Not Used
X Comm Fault
XComm Idle
XXXXXXXXX Not Used
Single/Three Ph Parameter No. 15
This parameter configures the DeviceNet
Module for single- or three-phase application.
This parameter should be set to “Single Phase"
when Bulletin 193S or 592S devices are
employed.
Access Rule Get/Set
Data Type BOOL
Group Advanced Setup
Units —
Min. Value 0 = Single-Phase
Max. Value 1 = Three-Phase
Default Value 1