4-2 Device Parameters
Parameter Group Listing
The 193-EDN DeviceNet Module contains six parameter groups
Monitor Group
Table 4.1 Parameter Groups
Monitor
parameters
Advanced Setup Reset/Lock DeviceNet Setup I/O Setup Trip History
1 Average %FLA 12 Trip Enable 14 Trip Reset 26 AutoBaudEnable 34 OutA Pr FltState 5 Trip Log 0
2%Therm Utilized 13 Warning Enable 24 Program Lock 27 NonVol Baud Rate 35 OutA Pr FltValue 6 Trip Log 1
3 Trip Status 15 Single/Three Ph 25 Set to Defaults 28 Output Assembly 36 OutA DN FltState 7 Trip Log 2
4 Warning Status 16 OL Reset Mode 29 Input Assembly 37 OutA DN FltValue 8 Trip Log 3
10 Device Status 17 OL Warning Level 30 Prod Assy Word 0 38 OutA DN IdlState 9 Trip Log 4
11 Firmware 18 Jam Inhibit Time 31 Prod Assy Word 1 39 OutA DN IdlValue
19 Jam Trip Delay 32 Prod Assy Word 2 40 IN1 Assignment
20 Jam Trip Level 33 Prod Assy Word 3 41 IN2 Assignment
21 Jam Warn Level
22 UL Inhibit Time
23 UL Warn Level
Average %FLA Parameter No. 1
This parameter reports the average motor current.
The value is reported as a percentage of motor rated
current (dial setting on the E1 Plus Overload Relay),
and is reported in increments of 5.
Access Rule Get
Data Type UINT
Group Monitor
Units %FLA
Min. Value 0
Max. Value 1275
Default Value None
% Therm Utilized Parameter No. 2
This parameter reports the percent thermal
utilization of the connected motor.
Access Rule Get
Data Type USINT
Group Monitor
Units %
Min. Value 0
Max. Value 100
Default Value None