Owner manual
Publication 193-UM006A-EN-P – October 2005
3-2 DeviceNet Node Commissioning
Figure 3.1 Network Online Screen
6. If RSNetWorx recognizes the device as an E1 Plus Overload Relay, skip
ahead to the following section - Using the Node Commissioning Tool of
RSNetWorx for DeviceNet.
Building and Registering an EDS File
The EDS file defines how RSNetWorx for DeviceNet will communicate to the
E1 Plus DeviceNet Module. The EDS file can be created over the DeviceNet
network or downloaded from the Internet.
Note: You can download the EDS file from www.ab.com/networks.eds
.
Do the following to build and register the EDS file:
1. Right-click on the “Unrecognized Device” icon. Select Register Device
from the menu that appears.
2. The EDS Wizard will appear.
3. Select Next.
4. Select Create an EDS File.
5. Select Next. The following screen appears: